This isolated barrier is used for intrinsic safety applications. 1-channel isolated barrier, 115/230 V AC supply, Input for approved dry contacts or SN/S1N sensors, Relay contact output, Fault indication output, Line fault detection (LFD), Up to SIL 3 acc. to IEC 61508, Up to PL d acc. to EN/ISO 13849pa. The device transfers digital signals (SN/S1N proximity sensors or approved dry contacts) from a hazardous area to a safe area. The input controls 1 relay contact output with 3 NO contacts (1 output is in series to the both output relays for the safety function), 1 relay contact output with 1 NO contact, and 1 passive transistor output (fault indication output). Unlike an SN/S1N series proximity sensor, a mechanical contact requires a 10 kΩ resistor to be placed across the contact in addition to a 1.5 kΩ resistor in series. Lead breakage (LB) and short circuit (SC) conditions of the control circuit are continuously monitored. During an fault condition, the fault indication output energizes and outputs I and II de-energize. For safety applications up to SIL 3, output I must be used. For safety applications up to SIL 2, output I and output II can be used.

Parametry techniczne

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 3
Performance level (PL): PL d
Connection: terminals 22, 23, 24
Rated voltage: 85 ... 253 V AC , 45 ... 65 Hz
Rated current: 30 mA ± 5 mA
Power dissipation: 2.2 W
Power consumption: max. 2.3 W
Connection side: field side
Connection: terminals 10+, 12-
Open circuit voltage/short-circuit current: approx. 8.4 V DC / approx. 11.7 mA
Lead resistance: ≤ 50 Ω, in hazardous area cable capacitances and inductivities are to be taken into account
Switching point: Relay de-energized: I < 2.1 mA and I > 5.9 mA
Switching point: Relay energized: 2.8 mA < I < 5.3 mA
Response delay: ≤ 1 ms
Connection side: control side
Connection: output I: terminals 13, 14 ; output II: terminals 15, 21 ; output III: terminals 16+, 17-
Output I: relay , signal
Switching point: Contact loading: 253 V AC/1 A/cos φ ≥ 0.7; 24 V DC/1 A resistive load
Switching point: Mechanical life: 50 x 106 switching cycles
Output II: relay , signal
Switching point: Contact loading: 253 V AC/1 A/cos φ ≥ 0.7; 24 V DC/1 A resistive load
Switching point: Mechanical life: 50 x 106 switching cycles
Output III: electronic output, passive , fault signal
Switching point: Rated voltage: 10 ... 30 V DC
Switching point: Signal level: 1-signal: (L+) -2.5 V (7 mA, short-circuit proof) / 0-signal: blocked output (Leakage current ≤ 10 mA)
Switching frequency: 5 Hz
Display elements: LEDs
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Machinery Directive: Directive 2006/42/EC: EN/ISO 13849-1:2008
Electromagnetic compatibility: NE 21:2011
Degree of protection: IEC 60529:2001
Safety: IEC/EN 61508:2010
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 280 g
Dimensions: 40 x 93 x 115 mm (1.6 x 3.7 x 4.5 inch) , housing type E
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: PTB 00 ATEX 2043
Machinery Directive: Marking: II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]
Machinery Directive: Input: EEx ia IIC
Machinery Directive: Voltage: 9.56 V
Machinery Directive: Current: 16.8 mA
Machinery Directive: Power: 41 mW (linear characteristic)
Supply: Maximum safe voltage: 253 V AC/DC (Attention! The rated voltage can be lower.)
Output: Contact loading: 253 V AC/1 A/cos φ ≥ 0.7; 24 V DC/1 A resistive load
Output: Maximum safe voltage: output I/output II: 253 V AC/DC (Attention! Um is no rated voltage.)
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: DE
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m