Pepperl+Fuchs 288593

VBA-2A-KE5-IL/UL

AS-Interface analog module

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

Switch cabinet module. Two analog outputsfa. The AS-Interface connecting module VBA-2A-KE5-IL/UL is a switch cabinet module with 2 analog outputs. The housing is only 19 mm wide and takes up little space in the switch cabinet. The module is mounted by snapping it onto the 35 mm DIN rail in compliance with. EN 50022. The connection is made via removable 4-pin push-in terminal blocks. For AS-i+, AS-i-, AUX+, and AUX-, two connections are available in each case; these connections are bridged in the terminal block. If the terminal block is disconnected from the module, the link between these connections is retained. The terminal blocks are mechanically coded. The power to the outputs and the connected actuators is supplied via the external UAUX voltage source. The relevant OUT LED displays the current switching status of the outputs. The OUT LEDs also indicate a lead breakage or an output value outside of the value range at the output. Notes:. The device is equipped with a communication monitor, which sets the outputs to zero if the AS-Interface does not communicate with the module for more than 40 ms. The communication monitor can be deactivated via the parameter P0. The output mode of current or voltage output is configured via the parameters P1 and P3 or via the terminals CON1 and CON2. A wire break at the current output, an output value outside of the value range, or an overload of the actuator supply cause a peripheral fault. The parameter P2 determines whether a peripheral fault is reported to the AS-Interface master. The communication via AS-Interface remains unaffected. If an overload occurs on the actuator supply, the outputs are set to zero.

Технические характеристики

Slave type: Standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
MTBF: 197 a
LED FAULT: Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault
LED PWR: AS-Interface voltage; green LED Green: voltage OK Flashing green: address 0 or peripheral error
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED OUT: Status of output signal; yellow LED Yellow: output value within value range Continually on: current mode 1.4 s on/0.1 s off: voltage mode Flashing yellow: wire break (at current output) or output value outside of value range
Auxiliary voltage (output): 24 V DC ± 15 % PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 75 mA
Protection class: III
Current consumption: IAUX ≤ 650 mA
Surge protection: UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Number/Type: Two analog outputs Current: 0 mA ... 20 mA Voltage: 0 V ... 10 V
Supply: From auxiliary voltage UAUX
Load: voltage output: min. 1 kΩ current output: max. 600 Ω
Current loading capacity: ≤ 600 mA (signal current + actuator power supply) from external auxiliary voltage UAUX, overload-proof and short-circuit proof
Resolution: Voltage output: 3 mV Current output: 6 µA
Accuracy: 0.15 % of full-scale value
Temperature influence: 1 µA/K or 0,3 mV/K
Short-circuit current: voltage output: max. 22 mA
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Profile: S-7.3.5
IO code: 7
ID code: 3
ID1 code: F
ID2 code: 5
Data bits (function via AS-Interface): The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Watchdog: P0=1 (default), watchdog active P0=0, watchdog inactive
Electromagnetic compatibility: P1: Output mode O1: P1=1 (default), current output P1=0, voltage output
Electromagnetic compatibility: P2: Indication of peripheral fault: P2=1 (default), peripheral fault is reported P2=0, peripheral fault is not reported
Electromagnetic compatibility: P3: Output mode O2: P3=1 (default), current output P3=0, voltage output
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Shock and impact resistance: 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance: 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree: 2
Degree of protection: IP20
Connection: Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material: Housing: PA 66-FR
Mass: 110 g
Mounting: DIN mounting rail
Note: Max. length of jumpers = 5 cm

Логистические характеристики

ТН ВЭД:
Страна происхождения: Singapur
EAN: 4050143049011
Вес: 0,13 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m