Pepperl+Fuchs 288593

VBA-2A-KE5-IL/UL

AS-Interface analog module

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

Switch cabinet module. Two analog outputsfa

Parámetros técnicos

Slave type: Standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
MTBF: 197 a
LED FAULT: Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault
LED PWR: AS-Interface voltage; green LED Green: voltage OK Flashing green: address 0 or peripheral error
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED OUT: Status of output signal; yellow LED Yellow: output value within value range Continually on: current mode 1.4 s on/0.1 s off: voltage mode Flashing yellow: wire break (at current output) or output value outside of value range
Auxiliary voltage (output): 24 V DC ± 15 % PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 75 mA
Protection class: III
Current consumption: IAUX ≤ 650 mA
Surge protection: UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Number/Type: Two analog outputs Current: 0 mA ... 20 mA Voltage: 0 V ... 10 V
Supply: From auxiliary voltage UAUX
Load: voltage output: min. 1 kΩ current output: max. 600 Ω
Current loading capacity: ≤ 600 mA (signal current + actuator power supply) from external auxiliary voltage UAUX, overload-proof and short-circuit proof
Resolution: Voltage output: 3 mV Current output: 6 µA
Accuracy: 0.15 % of full-scale value
Temperature influence: 1 µA/K or 0,3 mV/K
Short-circuit current: voltage output: max. 22 mA
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Profile: S-7.3.5
IO code: 7
ID code: 3
ID1 code: F
ID2 code: 5
Data bits (function via AS-Interface): The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Watchdog: P0=1 (default), watchdog active P0=0, watchdog inactive
Electromagnetic compatibility: P1: Output mode O1: P1=1 (default), current output P1=0, voltage output
Electromagnetic compatibility: P2: Indication of peripheral fault: P2=1 (default), peripheral fault is reported P2=0, peripheral fault is not reported
Electromagnetic compatibility: P3: Output mode O2: P3=1 (default), current output P3=0, voltage output
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Shock and impact resistance: 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance: 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree: 2
Degree of protection: IP20
Connection: Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material: Housing: PA 66-FR
Mass: 110 g
Mounting: DIN mounting rail
Note: Max. length of jumpers = 5 cm

Parámetros logísticos

ECCN:
País de origen: Singapur
EAN: 4050143049011
Peso: 0,13 kg
Longitud: 0,00 m
Anchura: 0,00 m