Pepperl+Fuchs 131000

HD2-DM-A

Fieldbus Power Hub, Advanced Diagnostic Module

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

Comprehensive diagnostics for fieldbus physical layer and power supply, Plug-in Module for the FieldConnex Power Hub, Precise measurements through passive circuits, For commissioning, online monitoring and troubleshooting, For FOUNDATION Fieldbus H1 and PROFIBUS PApa. Designed as a plug-in module for the FieldConnex® Power Hub, this Advanced Diagnostic Module (ADM) is a comprehensive measurement tool for the physical layer of up to four fieldbus segments. It's passive input circuits leave the physical layer untouched for exact data. The ADM detects gradual or sudden changes and helps trace even intermittent malfunctions. The ADM supports commissioning, online monitoring and troubleshooting. It can be integrated tightly into the DCS and PAM via a separate diagnostic bus, making the fieldbus physical layer itself a managable asset. Configuration tools automate setup of the ADM and of selected DCS. The Diagnostic Manager is the software for display and operation from the safety of the control room. The Professional Edition provides powerful functions and wizards simplifying and automating work procedures: an embedded expert system, a data historian, and a built-in oscilloscope (see datasheet DTM-FC.AD*).

Технические характеристики

Design / Mounting: Motherboard based
Rated voltage: 19.2 ... 35 V
Rated current: 110 ... 30 mA
Power dissipation: max. 2 W
Number of segments: 4
Fieldbus type: FOUNDATION Fieldbus/PROFIBUS PA
Rated voltage: 9 ... 32 V
LED PRI PWR: green: on, primary bulk power supply connected
LED SEC PWR: green: on, secondary bulk power supply connected
LED Seg 1...4: yellow: bus activity; red 2 Hz flashing: alarm; red: hardware error
Fault signal: VFC alarm 1 A, 50 V DC, normally closed
DIP switch: diagnostic address 1...247, binary coded
Interface type: diagnostic bus: RS 485
Fieldbus segment/Fieldbus segment: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Fieldbus segment/Supply: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013
Electromagnetic compatibility: NE 21:2011
Degree of protection: IEC 60529
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Ambient temperature: -40 ... 70 °C (-40 ... 158 °F)
Storage temperature: -40 ... 85 °C (-40 ... 185 °F)
Relative humidity: < 95 % non-condensing
Shock resistance: 15 g 11 ms
Vibration resistance: 1 g , 10 ... 150 Hz
Pollution degree: max. 2, according to IEC 60664
Corrosion resistance: acc. to ISA-S71.04-1985, severity level G3
Connection type: motherboard specific
Core cross-section: motherboard specific
Housing material: Polycarbonate
Housing width: 18 mm
Housing height: 106 mm
Housing depth: 128 mm
Degree of protection: IP20
Mass: approx. 100 g
Mounting: motherboard mounting
Mating cycles: 100
Certificate: TÜV 04 ATEX 2500 X
Electromagnetic compatibility: Marking: II 3 G Ex nA IIC T4 Gc
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
FM approval: FM certificate: FM 19 US 0015 X and FM 19 CA 0011 X
FM approval: FM marking: AEx/Ex ec IIC T4
IECEx approval: IECEx certificate: IECEx TUN 13.0038X
IECEx approval: IECEx marking: Ex nA IIC T4 Gc
Marine approval: DNV A-14038
Patents: This product may be covered by the following patent: US7,698,103
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m