250382
FDH-1
Fieldbus Diagnostic Handheld
Fieldbus Diagnostic Handheld, Comprehensive diagnostics for the fieldbus physical layer, Handheld with display and integrated expert system, Fieldbus interface Ex ia, FISCO, Entity, and DART, For commissioning, online monitoring and troubleshooting, For FOUNDATION Fieldbus H1 and PROFIBUS PApa
| Design / Mounting: | Handheld/mobile |
| Connection: | Fieldbus , Battery , 9V 6LR61 block, type alkaline, carbon-zinc, lithium iron disulfide, nickel-cadmium, nickel-metal hydride, or rechargeable lithium , USB |
| Fieldbus type: | FOUNDATION Fieldbus/PROFIBUS PA |
| Rated voltage: | 8.5 ... 35 V |
| Rated current: | ... 10 mA , if bus powered |
| Display: | LC display |
| Keypad: | Membrane 8 keys |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 |
| Electromagnetic compatibility: | NE 21:2011 |
| Degree of protection: | IEC 60529 |
| Shock resistance: | EN 60068-2-27 |
| Vibration resistance: | EN 60068-2-6 |
| Languages: | English (default), German (optional), Portuguese (optional), |
| Ambient temperature: | -20 ... 50 °C (-4 ... 122 °F) |
| Storage temperature: | -20 ... 70 °C (-4 ... 158 °F) |
| Relative humidity: | < 95 % non-condensing |
| Shock resistance: | 15 g , 11 ms |
| Vibration resistance: | 1 g , 10 ... 150 Hz |
| Connection type: | Fieldbus: Cable with test clips and cable with test plugs, 2.5 mm Trigger output: Cable with 2 banana plugs USB: Square type B socket |
| Degree of protection: | IP44 |
| Mass: | 500 g |
| EU-Type Examination Certificate: | ZELM 14 ATEX 0531 |
| Electromagnetic compatibility: Marking: | II 2(1) G Ex ib [ia Ga] IIC T4 Gb , II 3(1) G Ex ic [ia Ga] IIC T4 Gc , II 3 G Ex ic IIC T4 Gc , II (1 D) [Ex ia IIIC Da] , II (3 D) [Ex ic IIIC Dc] |
| Bus: Type: | Fieldbus |
| Bus: Type of protection: | ia, ib |
| Bus: Internal capacitance: | < 1.8 nF |
| Bus: Internal inductance: | < 1.5 µH |
| Bus: Voltage Ui: | 30 V |
| Bus: Type: | Fieldbus |
| Bus: Type of protection: | ic |
| Bus: Internal capacitance: | < 1.8 F |
| Bus: Internal inductance: | < 1.5 µH |
| Bus: Voltage Ui: | 35 V |
| Outputs: Type: | Trigger output |
| Outputs: Maximum safe voltage: | 140 V |
| Interface: Type: | USB interface |
| Interface: Maximum safe voltage: | 253 V |
| Interface: Voltage Ui: | 6 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012 , EN 60079-11:2012 |
| CSA approval: | CSA 16.70029275 |
| Directive conformity: Approved for: | Class I, Division 2, Groups A, B, C, D T4 Associated equipment for Class I, Division 1 |
| IECEx approval: | IECEx ZLM 14.0012 |
| Directive conformity: Approved for: | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ic IIC T4 Gc , [Ex ia IIIC Da] , [Ex ic IIIC Dc] |
| ECCN: | |
| País de origen: | SG |
| EAN: | |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |