Pepperl+Fuchs 250382

FDH-1

Fieldbus Diagnostic Handheld

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

Fieldbus Diagnostic Handheld, Comprehensive diagnostics for the fieldbus physical layer, Handheld with display and integrated expert system, Fieldbus interface Ex ia, FISCO, Entity, and DART, For commissioning, online monitoring and troubleshooting, For FOUNDATION Fieldbus H1 and PROFIBUS PApa

Parámetros técnicos

Design / Mounting: Handheld/mobile
Connection: Fieldbus , Battery , 9V 6LR61 block, type alkaline, carbon-zinc, lithium iron disulfide, nickel-cadmium, nickel-metal hydride, or rechargeable lithium , USB
Fieldbus type: FOUNDATION Fieldbus/PROFIBUS PA
Rated voltage: 8.5 ... 35 V
Rated current: ... 10 mA , if bus powered
Display: LC display
Keypad: Membrane 8 keys
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013
Electromagnetic compatibility: NE 21:2011
Degree of protection: IEC 60529
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Languages: English (default), German (optional), Portuguese (optional),
Ambient temperature: -20 ... 50 °C (-4 ... 122 °F)
Storage temperature: -20 ... 70 °C (-4 ... 158 °F)
Relative humidity: < 95 % non-condensing
Shock resistance: 15 g , 11 ms
Vibration resistance: 1 g , 10 ... 150 Hz
Connection type: Fieldbus: Cable with test clips and cable with test plugs, 2.5 mm Trigger output: Cable with 2 banana plugs USB: Square type B socket
Degree of protection: IP44
Mass: 500 g
EU-Type Examination Certificate: ZELM 14 ATEX 0531
Electromagnetic compatibility: Marking: II 2(1) G Ex ib [ia Ga] IIC T4 Gb , II 3(1) G Ex ic [ia Ga] IIC T4 Gc , II 3 G Ex ic IIC T4 Gc , II (1 D) [Ex ia IIIC Da] , II (3 D) [Ex ic IIIC Dc]
Bus: Type: Fieldbus
Bus: Type of protection: ia, ib
Bus: Internal capacitance: < 1.8 nF
Bus: Internal inductance: < 1.5 µH
Bus: Voltage Ui: 30 V
Bus: Type: Fieldbus
Bus: Type of protection: ic
Bus: Internal capacitance: < 1.8 F
Bus: Internal inductance: < 1.5 µH
Bus: Voltage Ui: 35 V
Outputs: Type: Trigger output
Outputs: Maximum safe voltage: 140 V
Interface: Type: USB interface
Interface: Maximum safe voltage: 253 V
Interface: Voltage Ui: 6 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012 , EN 60079-11:2012
CSA approval: CSA 16.70029275
Directive conformity: Approved for: Class I, Division 2, Groups A, B, C, D T4 Associated equipment for Class I, Division 1
IECEx approval: IECEx ZLM 14.0012
Directive conformity: Approved for: Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ic IIC T4 Gc , [Ex ia IIIC Da] , [Ex ic IIIC Dc]