Pepperl+Fuchs 250382

FDH-1

Fieldbus Diagnostic Handheld

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The FieldConnex. Fieldbus Diagnostic Handheld FDH‑1 is a comprehensive measurement and commissioning tool. The handheld can be connected to any point of a segment. Via display and push buttons, FDH‑1 guides the user through many scenarios of testing. FDH‑1 can record and store data for up to 32 segments with maximum device count without requiring a connection to a PC. Fieldbus Diagnostic Handheld, Comprehensive diagnostics for the fieldbus physical layer, Handheld with display and integrated expert system, Fieldbus interface Ex ia, FISCO, Entity, and DART, For commissioning, online monitoring and troubleshooting, For FOUNDATION Fieldbus H1 and PROFIBUS PApa. FDH‑1 supports inexperienced and expert users alike through different operating modes. Failure margin checks and device coupler tests help set up the optimum condition of the fieldbus infrastructure and find weak spots in the installation. The expert system and wizards enable easy handling and require little or no training. FDH‑1 supports multiple languages that can be downloaded onto the handheld. FDH‑1 Manager Software Premium can operate the handheld with enhanced visualization. The software loads data from FDH‑1 and saves data back, to allow for comparisons between actual and planned physical layer attributes.

Parametry techniczne

Design / Mounting: Handheld/mobile
Connection: Fieldbus , Battery , 9V 6LR61 block, type alkaline, carbon-zinc, lithium iron disulfide, nickel-cadmium, nickel-metal hydride, or rechargeable lithium , USB
Fieldbus type: FOUNDATION Fieldbus/PROFIBUS PA
Rated voltage: 8.5 ... 35 V
Rated current: ... 10 mA , if bus powered
Display: LC display
Keypad: Membrane 8 keys
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013
Electromagnetic compatibility: NE 21:2011
Degree of protection: IEC 60529
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Languages: English (default), German (optional), Portuguese (optional),
Ambient temperature: -20 ... 50 °C (-4 ... 122 °F)
Storage temperature: -20 ... 70 °C (-4 ... 158 °F)
Relative humidity: < 95 % non-condensing
Shock resistance: 15 g , 11 ms
Vibration resistance: 1 g , 10 ... 150 Hz
Connection type: Fieldbus: Cable with test clips and cable with test plugs, 2.5 mm Trigger output: Cable with 2 banana plugs USB: Square type B socket
Degree of protection: IP44
Mass: 500 g
EU-Type Examination Certificate: ZELM 14 ATEX 0531
Electromagnetic compatibility: Marking: II 2(1) G Ex ib [ia Ga] IIC T4 Gb , II 3(1) G Ex ic [ia Ga] IIC T4 Gc , II 3 G Ex ic IIC T4 Gc , II (1 D) [Ex ia IIIC Da] , II (3 D) [Ex ic IIIC Dc]
Bus: Type: Fieldbus
Bus: Type of protection: ia, ib
Bus: Internal capacitance: < 1.8 nF
Bus: Internal inductance: < 1.5 µH
Bus: Voltage Ui: 30 V
Bus: Type: Fieldbus
Bus: Type of protection: ic
Bus: Internal capacitance: < 1.8 F
Bus: Internal inductance: < 1.5 µH
Bus: Voltage Ui: 35 V
Outputs: Type: Trigger output
Outputs: Maximum safe voltage: 140 V
Interface: Type: USB interface
Interface: Maximum safe voltage: 253 V
Interface: Voltage Ui: 6 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012 , EN 60079-11:2012
CSA approval: CSA 16.70029275
Directive conformity: Approved for: Class I, Division 2, Groups A, B, C, D T4 Associated equipment for Class I, Division 1
IECEx approval: IECEx ZLM 14.0012
Directive conformity: Approved for: Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ic IIC T4 Gc , [Ex ia IIIC Da] , [Ex ic IIIC Dc]

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m