250382
FDH-1
Fieldbus Diagnostic Handheld
The FieldConnex. Fieldbus Diagnostic Handheld FDH‑1 is a comprehensive measurement and commissioning tool. The handheld can be connected to any point of a segment. Via display and push buttons, FDH‑1 guides the user through many scenarios of testing. FDH‑1 can record and store data for up to 32 segments with maximum device count without requiring a connection to a PC. Fieldbus Diagnostic Handheld, Comprehensive diagnostics for the fieldbus physical layer, Handheld with display and integrated expert system, Fieldbus interface Ex ia, FISCO, Entity, and DART, For commissioning, online monitoring and troubleshooting, For FOUNDATION Fieldbus H1 and PROFIBUS PApa. FDH‑1 supports inexperienced and expert users alike through different operating modes. Failure margin checks and device coupler tests help set up the optimum condition of the fieldbus infrastructure and find weak spots in the installation. The expert system and wizards enable easy handling and require little or no training. FDH‑1 supports multiple languages that can be downloaded onto the handheld. FDH‑1 Manager Software Premium can operate the handheld with enhanced visualization. The software loads data from FDH‑1 and saves data back, to allow for comparisons between actual and planned physical layer attributes.
| Design / Mounting: | Handheld/mobile |
| Connection: | Fieldbus , Battery , 9V 6LR61 block, type alkaline, carbon-zinc, lithium iron disulfide, nickel-cadmium, nickel-metal hydride, or rechargeable lithium , USB |
| Fieldbus type: | FOUNDATION Fieldbus/PROFIBUS PA |
| Rated voltage: | 8.5 ... 35 V |
| Rated current: | ... 10 mA , if bus powered |
| Display: | LC display |
| Keypad: | Membrane 8 keys |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 |
| Electromagnetic compatibility: | NE 21:2011 |
| Degree of protection: | IEC 60529 |
| Shock resistance: | EN 60068-2-27 |
| Vibration resistance: | EN 60068-2-6 |
| Languages: | English (default), German (optional), Portuguese (optional), |
| Ambient temperature: | -20 ... 50 °C (-4 ... 122 °F) |
| Storage temperature: | -20 ... 70 °C (-4 ... 158 °F) |
| Relative humidity: | < 95 % non-condensing |
| Shock resistance: | 15 g , 11 ms |
| Vibration resistance: | 1 g , 10 ... 150 Hz |
| Connection type: | Fieldbus: Cable with test clips and cable with test plugs, 2.5 mm Trigger output: Cable with 2 banana plugs USB: Square type B socket |
| Degree of protection: | IP44 |
| Mass: | 500 g |
| EU-Type Examination Certificate: | ZELM 14 ATEX 0531 |
| Electromagnetic compatibility: Marking: | II 2(1) G Ex ib [ia Ga] IIC T4 Gb , II 3(1) G Ex ic [ia Ga] IIC T4 Gc , II 3 G Ex ic IIC T4 Gc , II (1 D) [Ex ia IIIC Da] , II (3 D) [Ex ic IIIC Dc] |
| Bus: Type: | Fieldbus |
| Bus: Type of protection: | ia, ib |
| Bus: Internal capacitance: | < 1.8 nF |
| Bus: Internal inductance: | < 1.5 µH |
| Bus: Voltage Ui: | 30 V |
| Bus: Type: | Fieldbus |
| Bus: Type of protection: | ic |
| Bus: Internal capacitance: | < 1.8 F |
| Bus: Internal inductance: | < 1.5 µH |
| Bus: Voltage Ui: | 35 V |
| Outputs: Type: | Trigger output |
| Outputs: Maximum safe voltage: | 140 V |
| Interface: Type: | USB interface |
| Interface: Maximum safe voltage: | 253 V |
| Interface: Voltage Ui: | 6 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012 , EN 60079-11:2012 |
| CSA approval: | CSA 16.70029275 |
| Directive conformity: Approved for: | Class I, Division 2, Groups A, B, C, D T4 Associated equipment for Class I, Division 1 |
| IECEx approval: | IECEx ZLM 14.0012 |
| Directive conformity: Approved for: | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ic IIC T4 Gc , [Ex ia IIIC Da] , [Ex ic IIIC Dc] |
| ECCN: | |
| Kraj pochodzenia: | SG |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |