244950
VBA-2A-G10-E2L-1M-2V1-W
AS-Interface actuator module
G10 ultra compact module. 2 outputsfa
| Slave type: | A/B slave |
| AS-Interface specification: | V3.0 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E223772 "For use in NFPA 79 Applications only" |
| MTTFd: | 516 a |
| LED FAULT: | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing |
| LED AS-i: | AS-Interface voltage; LED green |
| LED OUT: | Switching state (output); 2 LED yellow |
| Auxiliary voltage: | 20 ... 30 V DC PELV |
| Rated operating voltage: | 18.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 40 mA / max. 60 mA |
| Protection class: | III |
| Surge protection: | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
| Number/Type: | 2 electronic outputs, PNP, overload and short-circuit proof |
| Supply: | from external auxiliary voltage UAUX |
| Current: | 2 A per output, TB ≤ 40°C: 4 A total, 40°C < TB ≤ 70°C: 3 A total , overload and short-circuit protected |
| Voltage: | ≥ (UAUX - 0.5 V) |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Electrical safety: | IEC 61140:2004 |
| Emitted interference: | EN 61000-6-4:2007 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61000-6-2:2005 EN 62026-2:2013 |
| Profile: | S-8.A.E |
| IO code: | 8 |
| ID code: | A |
| ID1 code: | 7 |
| ID2 code: | E |
| Data bits (function via AS-Interface): | input output |
| Electromagnetic compatibility: D0: | - OUT1 |
| Electromagnetic compatibility: D1: | - OUT2 |
| Electromagnetic compatibility: D2: | - - |
| Electromagnetic compatibility: D3: | - - |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
| Electromagnetic compatibility: P1: | not used |
| Electromagnetic compatibility: P2: | Lead breakage outputs P2 = 0 lead breakage on P2 = 1 lead breakage off (default settings) |
| Electromagnetic compatibility: P3: | not used |
| UL approval: | cULus Listed, Type 1 enclosure |
| Electromagnetic compatibility: Maximum permissible ambient temperature: | max. 65 °C (max. 149 °F) |
| Ambient temperature: | -40 ... 70 °C (-40 ... 158 °F) |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Shock and impact resistance: | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
| Vibration resistance: | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Degree of protection: | IP67 IP67 / IP68 / IP69K with flat cable VAZ-FK-S-* |
| Connection: | AS-Interface/UAUX: AS-Interface flat cable Outputs & matching connector: M12 round connector, 4-pin, A-coded, according to IEC 61076-2-101:2012 |
| Material: Contacts: | CuSn / Au |
| Material: Housing: | PBT PC |
| Material: Body: | black PUR |
| Material: Cable: | PUR |
| Material: Mounting screw: | Stainless steel 1.4305 / AISI 303 |
| Cable: Sheath diameter: | ∅4,3 mm |
| Cable: Color: | black |
| Cable: Cores: | 3 x 0.34 mm2 |
| Cable: Length: | 1 m |
| Mass: | 100 g |
| Tightening torque, fastening screws: | 1.65 Nm |
| Tightening torque, cable gland: | 0.4 Nm |
| ECCN: | |
| País de origen: | Indonesien |
| EAN: | 4050143039760 |
| Peso: | 0,11 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |