Pepperl+Fuchs 239920

KT-MB-GT2AD.FF.IO

Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface and I/O

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

System integration kit for Advanced Diagnostics, PCS integration via Diagnostic Manager or device DTM, Simple automatic setup of Advanced Diagnostics, Alarm handling and integrated I/O for cabinet monitoring/control, For FOUNDATION Fieldbus and PROFIBUS PApa

Parámetros técnicos

Design / Mounting: Motherboard based
Rated voltage: 19.2 ... 35 V DC SELV/PELV
Rated current: 210 ... 120 mA
Power dissipation: max. 4.2 W
Fieldbus type: FOUNDATION Fieldbus
Physical layer profile: profile type 114
ITK version: 6
Implementation: resource block 1x RS function block 4x MDI, 1x MDO, 1x MAI, 1x DI transducer block 16x ADM TB, 1x IO TB
Firmware update: Ethernet
Polarity: polarity-sensitive
Rated voltage: 9 ... 35 V SELV/PELV
Rated current: 0 mA
Rated voltage: max. 35 V SELV/PELV
Port: 100 BASE-TX
Protocol: TCP/IP and UDP/IP
Services: ICMP , DHCP , AutoIP , HTTP
Connection type: RJ-45 socket, 8-pin
Transfer rate: 100 MBit/s
Connection: only for the connection to protected circuits
Rated voltage: max. 35 V
Number of Diagnostic Bus Channels: 2
Number of Diagnostic Modules/Channel: 31 Using Ethernet Interface , 8 Using Fieldbus Interface
Termination: integrated
Cable length/Channel: 30 m
LED ERR: red: Hardware fault
LED PWR: green: Power on
Fault signal: buzzer on
LINK/ACT: yellow
CH1, CH2: yellow: diagnostic bus activity
Input I, II: Input type: selectable: Frequency input , NAMUR/mechanical contact
Frequency: Connection: only passive load
Frequency: Rated voltage: max. 35 V
Frequency: Input frequency: 0.3 Hz to 1 kHz
Frequency: Pulse duration: min. 50 µs
Frequency: Accuracy: ± 1 %
Frequency: Cable length: max. 30 m
Frequency: Line fault detection: lead breakage , short-circuit
NAMUR: Sensor type: NAMUR sensor according to IEC/EN 60947-5-6
NAMUR: Connection: only passive load
NAMUR: Rated voltage: max. 35 V
NAMUR: Switching frequency: 10 Hz
NAMUR: Cable length: max. 30 m
NAMUR: Line fault detection: lead breakage , short circuit
Input III, IV: Input type: NAMUR/mechanical contact
NAMUR: Sensor type: NAMUR sensor according to IEC/EN 60947-5-6
NAMUR: Connection: only passive load
NAMUR: Rated voltage: max. 35 V
NAMUR: Switching frequency: 10 Hz
NAMUR: Cable length: max. 30 m
NAMUR: Line fault detection: lead breakage , short circuit
Input V: Input type: selectable: diagnostic bus CH 1 alarm input , NAMUR/mechanical contact
Alarm Input: Connection: only passive load
Alarm Input: Rated voltage: max. 35 V
Alarm Input: Cable length: max. 30 m
Alarm Input: Line fault detection: lead breakage , short circuit
NAMUR: Sensor type: NAMUR sensor according to IEC/EN 60947-5-6
NAMUR: Connection: only passive load
NAMUR: Rated voltage: max. 35 V
NAMUR: Switching frequency: 10 Hz
NAMUR: Cable length: max. 30 m
NAMUR: Line fault detection: lead breakage , short circuit
Input VI: Input type: selectable: diagnostic bus CH 2 alarm input , NAMUR/mechanical contact
Alarm Input: Connection: only passive load
Alarm Input: Rated voltage: max. 35 V
Alarm Input: Cable length: max. 30 m
Alarm Input: Line fault detection: lead breakage , short-circuit
NAMUR: Sensor type: NAMUR sensor according to IEC/EN 60947-5-6
NAMUR: Connection: only passive load
NAMUR: Rated voltage: max. 35 V
NAMUR: Switching frequency: 10 Hz
NAMUR: Cable length: max. 30 m
NAMUR: Line fault detection: lead breakage , short circuit
Input VII, VIII: Input type: selectable: Pt100 4-wire temperature input , NAMUR/mechanical contact
Temperature: Connection: only passive load
Temperature: Rated voltage: max. 35 V
Temperature: Measurement range: -50 ... 90 °C (-58 ... 194 °F)
Temperature: Accuracy: 1 K
Temperature: Measuring current: 1 mA
Temperature: Lead resistance: 4.2 Ω per line
Temperature: Cable length: max. 30 m
Temperature: Line fault detection: lead breakage , short-circuit
NAMUR: Sensor type: NAMUR sensor according to IEC/EN 60947-5-6
NAMUR: Connection: only passive load
NAMUR: Rated voltage: max. 35 V
NAMUR: Switching frequency: 10 Hz
NAMUR: Cable length: max. 30 m
NAMUR: Line fault detection: lead breakage , short circuit
Humidity: Measurement range: 0 ... 95 % RH
Humidity: Accuracy: 2 % RH
Humidity: Resolution: 0.04 %
Output I: Output type: selectable: diagnostic bus CH 1 , relay , NO contact
Output I: Contact loading: 250 V AC/ 6 A resistive load
Output I: Mechanical life: 1 x 105 switching cycles
Output I: Response time: turn-on time 7 ms , turn-off time 3 ms
Output I: Switching frequency: 6 min-1 full load, 1200 min-1 without load
Output II: Output type: selectable: diagnostic bus CH 2 , relay , NO contact
Output II: Contact loading: 250 V AC/ 6 A resistive load
Output II: Mechanical life: 1 x 105 switching cycles
Output II: Response time: turn-on time 7 ms , turn-off time 3 ms
Output II: Switching frequency: 6 min-1 full load, 1200 min-1 without load
Output III: Output type: selectable: common alarm , volt-free contact , NC contact
Output III: Connection: only for the connection to protected circuits
Output III: Voltage: 50 V DC
Output III: Current: max. 1 A
Output IV: Output type: common alarm , buzzer
All circuits/FE: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output I, II/other circuits: functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Ethernet/Supply: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Ethernet/other circuits: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Fieldbus/other circuits: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Diagnostic Bus/other circuits: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013
Low voltage: Directive 73/23/EEC: EN 61010-1:2010
Galvanic isolation: IEC 62103
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Fieldbus standard: IEC 61158-2
Climatic conditions: DIN IEC 721
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Ethernet: IEEE 802.3
Ambient temperature: -40 ... 60 °C (-40 ... 140 °F) hazardous area -40 ... 70 °C (-40 ... 158 °F) safe area horizontal DIN rail mounting
Storage temperature: -40 ... 85 °C (-40 ... 185 °F)
Relative humidity: < 95 % non-condensing
Shock resistance: 5 g 11 ms
Vibration resistance: 1 g , 10 ... 150 Hz
Pollution degree: max. 2, according to IEC 60664
Corrosion resistance: acc. to ISA-S71.04-1985, severity level G3
Housing material: Polycarbonate
Housing width: see dimensions
Housing height: see dimensions
Housing depth: see dimensions
Degree of protection: IP20
Mass: 500 g
Mounting: DIN rail mounting
FOUNDATION Fieldbus: Connection: For connection to circuits with safe limited voltage according to IEC 60079-11:2011, type of protection "ic"
FOUNDATION Fieldbus: Voltage Ui: max. 35 V
Certificate: TÜV 14 ATEX 115980 X
FOUNDATION Fieldbus: Marking: Motherboard MB-FB-GT.AD.FF.IO II 3 G Ex nA nC IIC T4 Gc , Gateway II 3 G Ex nA IIC T4 Gc
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
IECEx approval: IECEx TUN 14.0003X
Directive conformity: Approved for: Motherboard Ex nA nC IIC T4 Gc , Gateway Ex nA IIC T4 Gc
Supplementary information: Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.