Pepperl+Fuchs 237500

VBA-4A-G11-I/U-F

AS-Interface analog module

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

G11 analog module. 4 analog outputsfa

Parámetros técnicos

Slave type: Standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
MTTFd: 220 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED AS-i/FAULT: Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault
LED ANALOG: Status of output signal; yellow LED Yellow: Output value within range Yellow flashing: lead breakage (on current output) or output value out of range
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED INT/EXT: status display output supply; LED green green: output supply from AS-Interface off: output supply from auxiliary voltage
Auxiliary voltage (output): 24 V DC ± 15 % PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 75 mA (without outputs) / max. 200 mA
Protection class: III
Surge protection: UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 analog outputs Current: 0 ... 20 mA Voltage: 0 ... 10 V
Supply: from AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT)
Load: voltage output: min. 1 kΩ current output: max. 600 Ω
Current loading capacity: ≤ 120 mA (signal current + actuator supply) from AS-Interface; overload and short-circuit protected ≤ 700 mA (signal current + actuator supply) from external bulk power supply UAUX, overload and short-circuit protected
Resolution: Voltage output: 3 mV Current output: 6 µA
Accuracy: 0.15 % of full-scale value
Temperature influence: 1 µA/K or 0,3 mV/K
Short-circuit current: voltage output: max. 22 mA
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Profile: S-7.3.6
IO code: 7
ID code: 3
ID1 code: F
ID2 code: 6
Data bits (function via AS-Interface): The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Watchdog: P0=1 (default), watchdog active P0=0, watchdog inactive
Electromagnetic compatibility: P1: Output mode: P1=1 (default), 4x current output P2=0, 4x voltage output
Electromagnetic compatibility: P2: Indication of peripheral fault: P2=1 (default), peripheral fault is reported P2=0, peripheral fault is not reported
Electromagnetic compatibility: P3: Automatic mode: P3=1 (default), manual setting of output mode P3=0, automatic load detection (mixed mode possible)
Ambient temperature: -25 ... 60 °C (-13 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Pollution degree: 3
Degree of protection: IP68 / IP69K
Connection: AS-Interface/UAUX: cable piercing method, flat cable yellow/flat cable black Outputs: M12 round connector
Material: Housing: PBT PC
Material: Mounting screw: Stainless steel 1.4305 / AISI 303
Mass: 200 g
Tightening torque, housing screws: 1.8 Nm
Tightening torque, cable gland: 0.4 Nm
Mounting: Mounting plate

Parámetros logísticos

ECCN:
País de origen: SG
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m