237500
VBA-4A-G11-I/U-F
AS-Interface analog module
G11 analog module. 4 analog outputsfa
| Slave type: | Standard slave |
| AS-Interface specification: | V3.0 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E223772 |
| MTTFd: | 220 a |
| Mission Time (TM): | 20 a |
| Diagnostic Coverage (DC): | 0 % |
| LED AS-i/FAULT: | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
| LED ANALOG: | Status of output signal; yellow LED Yellow: Output value within range Yellow flashing: lead breakage (on current output) or output value out of range |
| LED AUX: | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| LED INT/EXT: | status display output supply; LED green green: output supply from AS-Interface off: output supply from auxiliary voltage |
| Auxiliary voltage (output): | 24 V DC ± 15 % PELV |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 75 mA (without outputs) / max. 200 mA |
| Protection class: | III |
| Surge protection: | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
| Number/Type: | 4 analog outputs Current: 0 ... 20 mA Voltage: 0 ... 10 V |
| Supply: | from AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT) |
| Load: | voltage output: min. 1 kΩ current output: max. 600 Ω |
| Current loading capacity: | ≤ 120 mA (signal current + actuator supply) from AS-Interface; overload and short-circuit protected ≤ 700 mA (signal current + actuator supply) from external bulk power supply UAUX, overload and short-circuit protected |
| Resolution: | Voltage output: 3 mV Current output: 6 µA |
| Accuracy: | 0.15 % of full-scale value |
| Temperature influence: | 1 µA/K or 0,3 mV/K |
| Short-circuit current: | voltage output: max. 22 mA |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Emitted interference: | EN 61000-6-4:2007 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
| Profile: | S-7.3.6 |
| IO code: | 7 |
| ID code: | 3 |
| ID1 code: | F |
| ID2 code: | 6 |
| Data bits (function via AS-Interface): | The transfer of the data value is based on AS-Interface Profile 7.3. |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | Watchdog: P0=1 (default), watchdog active P0=0, watchdog inactive |
| Electromagnetic compatibility: P1: | Output mode: P1=1 (default), 4x current output P2=0, 4x voltage output |
| Electromagnetic compatibility: P2: | Indication of peripheral fault: P2=1 (default), peripheral fault is reported P2=0, peripheral fault is not reported |
| Electromagnetic compatibility: P3: | Automatic mode: P3=1 (default), manual setting of output mode P3=0, automatic load detection (mixed mode possible) |
| Ambient temperature: | -25 ... 60 °C (-13 ... 140 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 85 % , noncondensing |
| Climatic conditions: | For indoor use only |
| Altitude: | ≤ 2000 m above MSL |
| Pollution degree: | 3 |
| Degree of protection: | IP68 / IP69K |
| Connection: | AS-Interface/UAUX: cable piercing method, flat cable yellow/flat cable black Outputs: M12 round connector |
| Material: Housing: | PBT PC |
| Material: Mounting screw: | Stainless steel 1.4305 / AISI 303 |
| Mass: | 200 g |
| Tightening torque, housing screws: | 1.8 Nm |
| Tightening torque, cable gland: | 0.4 Nm |
| Mounting: | Mounting plate |
| ECCN: | |
| País de origen: | SG |
| EAN: | |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |