Opis

G11 analog module. 4 analog outputsfa. The analog module VBA-4A-G11-I/U-F has four analog outputs. They can be configured either as current outputs (0 mA .. 20 mA) or voltage outputs (0 V .. 10 V). Automatic output detection allows outputs to operate as a current or voltage output, depending on the existing load. The outputs are configured as current outputs on delivery from the factory. Power is supplied to the outputs through the yellow AS-Interface cable or auxiliary power, depending on the position of the DIP switch. Analog value conversion and data transfer are provided asynchronously according to AS-Interface profile 7.3. The rise time of the analog signals is approx. 2 ms. If a current output has the analog value “0”, lead breakages are not monitored on the respective channel. In this case, peripheral faults are not signaled when there is no active connection to an actuator. If the internal “watchdog” monitoring function is enabled, the output signals are reset to zero if communication with the AS-Interface fails. The G11 module with IP68/IP69K protection is particularly suitable for demanding field applictions. The connection to the actuators is established via M12 connectors. The module can be presddressed by connecting it to the handheld programming unit VBP-HH1 via the addressing socket. The connection to the AS-Interface transfer line is established using the AS-Interface flat cable. Note:. A lead breakage at a current output, an output value outside the value range or an overload of the actuator supply is transmitted to the AS-Interface master via the 'peripheral fault' function. Communication via the AS-Interface continues.

Parametry techniczne

Slave type: Standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
MTTFd: 220 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED AS-i/FAULT: Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault
LED ANALOG: Status of output signal; yellow LED Yellow: Output value within range Yellow flashing: lead breakage (on current output) or output value out of range
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED INT/EXT: status display output supply; LED green green: output supply from AS-Interface off: output supply from auxiliary voltage
Auxiliary voltage (output): 24 V DC ± 15 % PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 75 mA (without outputs) / max. 200 mA
Protection class: III
Surge protection: UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 analog outputs Current: 0 ... 20 mA Voltage: 0 ... 10 V
Supply: from AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT)
Load: voltage output: min. 1 kΩ current output: max. 600 Ω
Current loading capacity: ≤ 120 mA (signal current + actuator supply) from AS-Interface; overload and short-circuit protected ≤ 700 mA (signal current + actuator supply) from external bulk power supply UAUX, overload and short-circuit protected
Resolution: Voltage output: 3 mV Current output: 6 µA
Accuracy: 0.15 % of full-scale value
Temperature influence: 1 µA/K or 0,3 mV/K
Short-circuit current: voltage output: max. 22 mA
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Profile: S-7.3.6
IO code: 7
ID code: 3
ID1 code: F
ID2 code: 6
Data bits (function via AS-Interface): The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Watchdog: P0=1 (default), watchdog active P0=0, watchdog inactive
Electromagnetic compatibility: P1: Output mode: P1=1 (default), 4x current output P2=0, 4x voltage output
Electromagnetic compatibility: P2: Indication of peripheral fault: P2=1 (default), peripheral fault is reported P2=0, peripheral fault is not reported
Electromagnetic compatibility: P3: Automatic mode: P3=1 (default), manual setting of output mode P3=0, automatic load detection (mixed mode possible)
Ambient temperature: -25 ... 60 °C (-13 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Pollution degree: 3
Degree of protection: IP68 / IP69K
Connection: AS-Interface/UAUX: cable piercing method, flat cable yellow/flat cable black Outputs: M12 round connector
Material: Housing: PBT PC
Material: Mounting screw: Stainless steel 1.4305 / AISI 303
Mass: 200 g
Tightening torque, housing screws: 1.8 Nm
Tightening torque, cable gland: 0.4 Nm
Mounting: Mounting plate

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m