191610
KLD0-SAA
Voltage adjustment module
Series voltage reducing module, Removable terminals, Polarity reversal protected, Installation in cabinet on DIN mounting rail, For FOUNDATION Fieldbus H1 and PROFIBUS PApa
| Design / Mounting: | Cabinet installation |
| Field-side: Connection: | terminals 10+, 11-, 12S |
| Field-side: Rated voltage: | Uin - Uout 0.9 ... 1.8 V |
| Field-side: Rated current: | max. 1 A |
| Host-side: Connection: | terminals 7+, 8-, 9S |
| Host-side: Rated voltage: | 9 ... 32 V DC |
| Host-side: Rated current: | max. 1 A |
| Host-side: Power dissipation: | max. 1.8 W |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Relative humidity: | < 75 % |
| Pollution degree: | max. 2, according to IEC 60664 |
| Connection type: | Terminals |
| Core cross-section: | up to 2.5 mm2 |
| Housing: | 20 mm x 115 mm x 107 mm |
| Degree of protection: | IP20 |
| Mass: | approx. 100 g |
| Mounting: | DIN rail mounting |
| Statement of conformity: | PF 16 CERT 1030 X |
| Electromagnetic compatibility: Group, category, type of protection: | II 3 G Ex ec IIC T4 Gc |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012 , EN 60079-7:2015 |
| ECCN: | |
| País de origen: | DE |
| EAN: | |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |