Pepperl+Fuchs 188848

VAA-4E4A-G2-ZA/EA2

AS-Interface sensor/actuator module

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

G2 flat module. 4 inputs (PNP) and 4 electronic outputsfa

Parámetros técnicos

Slave type: Standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.0
UL File Number: E223772
MTTFd: 140 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED FAULT: error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs
LED PWR: AS-Interface voltage; LED green
LED AUX: ext. auxiliary voltage UAUX ; LED green
LED IN: switching state (input); 4 LED yellow
LED OUT: Switching state (output); 4 LED yellow
Auxiliary voltage (output): 20 ... 30 V DC PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 40 mA (without sensors) / max. 220 mA
Protection class: III
Surge protection: UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC
Supply: from AS-Interface
Voltage: 21 ... 31 V
Current loading capacity: ≤ 180 mA (TB ≤ 40 °C), ≤ 140 mA (TB ≤ 60 °C), , overload and short-circuit protected
Input current: ≤ 9 mA (limited internally)
Switching point: according to DIN EN 61131-2 (Type 2)
: 0 (unattenuated): ≤ 3 mA
: 1 (attenuated): ≥ 5 mA
Signal delay: < 2 ms (input/AS-Interface)
Signal frequency: ≤ 250 Hz
Number/Type: 4 electronic outputs, PNP, overload and short-circuit proof
Supply: from external auxiliary voltage UAUX
Current: 2 A per output Sum 4 A (TB ≤ 40 °C) Sum 3 A (TB ≤ 60 °C)
Voltage: ≥ (UAUX - 0.5 V)
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Input: EN 61131-2:2007
Emitted interference: EN 61000-6-4:2001
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2001
Profile: S-7.F
IO code: 7
ID code: F
ID1 code: F
ID2 code: E
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1 OUT1
Electromagnetic compatibility: D1: IN2 OUT2
Electromagnetic compatibility: D2: IN3 OUT3
Electromagnetic compatibility: D3: IN4 OUT4
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
Electromagnetic compatibility: P1: not used
Electromagnetic compatibility: P2: not used
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 60 °C (-13 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Pollution degree: 3
Degree of protection: IP67
Connection: Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector
Material: Housing: PBT
Mass: 150 g
Tightening torque, cable gland: 0.4 Nm
Mounting: Mounting plate

Parámetros logísticos

ECCN:
País de origen: SG
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m