188848
VAA-4E4A-G2-ZA/EA2
AS-Interface sensor/actuator module
The VAA-4E4A-G2-ZA/EA2 is an AS-Interface module with 4 Inputs and 4 outputs. Mechanical contacts (e. g. push buttons) as well as 2-, 3- and 4-wire sensors can be connected to the inputs. The outputs are electronic outputs, which can be collectively loaded with 24 V DC and 1 A per output. G2 flat module. 4 inputs (PNP) and 4 electronic outputsfa. The IP67 flat module is ideal for applications in the field. An addressing jack is integrated in the module. The connection for the sensors/actuators is via M12 x 1 screw connections. An LED is provided on the top of the module, for each channel, to indicate the current switching status. Similarly, an LED is provided to monitor the AS-Interface communication and to indicate that the module has the address 0. LEDs are also provided to indicate AS-Interface voltage and external power supply. The mounting plate U-G2FF is used as standard for the connection to the AS-Interface flat cable and the external 24 V DC supply. The specially designed base enables the user to connect flat cable from both sides. The device incorporates communication monitoring, which switches off power to the outputs if no communication has taken place on the AS-Interface line for longer than 40 ms. An overloading of the internal input supply or of the outputs is signalled to the AS-interface master via the "Peripheral fault" function. Communication via the AS-Interface remains intact. Note:. The mounting base for the module is sold separately.
| Slave type: | Standard slave |
| AS-Interface specification: | V3.0 |
| Required master specification: | ≥ V2.0 |
| UL File Number: | E223772 |
| MTTFd: | 140 a |
| Mission Time (TM): | 20 a |
| Diagnostic Coverage (DC): | 0 % |
| LED FAULT: | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs |
| LED PWR: | AS-Interface voltage; LED green |
| LED AUX: | ext. auxiliary voltage UAUX ; LED green |
| LED IN: | switching state (input); 4 LED yellow |
| LED OUT: | Switching state (output); 4 LED yellow |
| Auxiliary voltage (output): | 20 ... 30 V DC PELV |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 40 mA (without sensors) / max. 220 mA |
| Protection class: | III |
| Surge protection: | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
| Number/Type: | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC |
| Supply: | from AS-Interface |
| Voltage: | 21 ... 31 V |
| Current loading capacity: | ≤ 180 mA (TB ≤ 40 °C), ≤ 140 mA (TB ≤ 60 °C), , overload and short-circuit protected |
| Input current: | ≤ 9 mA (limited internally) |
| Switching point: | according to DIN EN 61131-2 (Type 2) |
| : 0 (unattenuated): | ≤ 3 mA |
| : 1 (attenuated): | ≥ 5 mA |
| Signal delay: | < 2 ms (input/AS-Interface) |
| Signal frequency: | ≤ 250 Hz |
| Number/Type: | 4 electronic outputs, PNP, overload and short-circuit proof |
| Supply: | from external auxiliary voltage UAUX |
| Current: | 2 A per output Sum 4 A (TB ≤ 40 °C) Sum 3 A (TB ≤ 60 °C) |
| Voltage: | ≥ (UAUX - 0.5 V) |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Input: | EN 61131-2:2007 |
| Emitted interference: | EN 61000-6-4:2001 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61000-6-2:2001 |
| Profile: | S-7.F |
| IO code: | 7 |
| ID code: | F |
| ID1 code: | F |
| ID2 code: | E |
| Data bits (function via AS-Interface): | input output |
| Electromagnetic compatibility: D0: | IN1 OUT1 |
| Electromagnetic compatibility: D1: | IN2 OUT2 |
| Electromagnetic compatibility: D2: | IN3 OUT3 |
| Electromagnetic compatibility: D3: | IN4 OUT4 |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
| Electromagnetic compatibility: P1: | not used |
| Electromagnetic compatibility: P2: | not used |
| Electromagnetic compatibility: P3: | not used |
| Ambient temperature: | -25 ... 60 °C (-13 ... 140 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 85 % , noncondensing |
| Climatic conditions: | For indoor use only |
| Altitude: | ≤ 2000 m above MSL |
| Pollution degree: | 3 |
| Degree of protection: | IP67 |
| Connection: | Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector |
| Material: Housing: | PBT |
| Mass: | 150 g |
| Tightening torque, cable gland: | 0.4 Nm |
| Mounting: | Mounting plate |
| ECCN: | |
| Kraj pochodzenia: | SG |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |