Pepperl+Fuchs 132964

KFD2-SR2-Ex2.W.SM

Monitor del sentido de rotación y punto muerto

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

Barrera aislada de 2 canales, Alimentación de 24 V CC (carril de alimentación), Entradas de contacto o NAMUR, Valores de desconexión de frecuencia seleccionables, 2 salidas de contacto de relé, Puenteado de arranque, Dirección de acción seleccionable, Supervisión de fallos de conducción, Hasta SIL 2 según IEC 61508pa

Parámetros técnicos

Signal type: Digital Input
Programming: via DIP switch and programmable
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 14+, 15-
Rated voltage: 20 ... 30 V DC
Power consumption: max. 1.5 W
Connection side: field side
Connection: Input I: terminals 1+, 2+, 3- ; Input II: terminals 4+, 5+, 6-
Rated values: acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current: approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection: breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Control input: sensor power supply approx. 8.2 V, impedance 1.2 kΩ
Pulse duration: > 200 µs for standstill monitoring, > 250 µs for rotation direction detecion
Connection side: control side
Connection: output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Contact loading: 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Minimum switch current: 2 mA / 24 V DC
Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Mechanical life: 107 switching cycles
Trip value: for standstill monitoring: 0.1 Hz; 0.5 Hz; 2 Hz; 10 Hz adjustable via DIP switch (S1 and S2)
Accuracy: 5 % (S3 = I), 30 % (S3 = II)
Start-up override: 5 seconds or 20 seconds, programmable
Frequency range: ≤ 2 kHz
Rotation direction detection: 90° phase difference between pulse input signal 1 and 2, overlapping ≥ 125 µs
Input/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Input: EN 60947-5-6:2000
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: PTB 00 ATEX 2080
Low voltage: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Low voltage: Input: Ex ia
Low voltage: Voltage: 10.5 V
Low voltage: Current: 13 mA
Low voltage: Power: 34 mW (linear characteristic)
Supply: Maximum safe voltage: 253 V AC / 125 V DC (Attention! Um is no rated voltage.)
Output: Contact loading: 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Output: Maximum safe voltage: 253 V AC (Attention! The rated voltage can be lower.)
Fault indication output: Maximum safe voltage: 40 V DC (Attention! Um is no rated voltage.)
Certificate: TÜV 99 ATEX 1493 X
Fault indication output: Marking: II 3G Ex ec nC IIC T4 Gc
Output: Contact loading: 50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
FM approval: FM certificate: FM19US0207X
FM approval: Control drawing: 116-0035
UL approval: E106378
FM approval: Control drawing: 116-0145
CSA approval: Control drawing: 116-0047
IECEx approval: IECEx certificate: IECEx PTB 11.0034 , IECEx TUN 19.0013X
IECEx approval: IECEx marking: [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)

Parámetros logísticos

ECCN:
País de origen: ID
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m