130713
R-SP-E12
Segment Protector for Cabinet Installation
Segment Protector for Cabinet Installation, 12 increased safety outputs (Ex e), Short circuit current limitation per output, Segment Protector in Zone 1/Div. 2, Instruments in Zone 1/Div. 1, For FOUNDATION Fieldbus H1 and PROFIBUS PApa
| Design / Mounting: | Cabinet installation |
| Power dissipation: | 250 mW |
| Main cable (Trunk): Rated voltage: | 9 ... 32 V DC |
| Outputs: Number of outputs: | 12 |
| Outputs: Rated voltage: | max. 32 V |
| Outputs: Rated current: | max. 40 mA |
| Outputs: Short-circuit current: | max. 52 mA |
| Self current consumption: | max. 9 mA |
| Voltage drop main cable/outputs: | max. 1.3 V |
| Terminating resistor: | selectable 100 Ω integrated |
| Surge protection: | trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V |
| LED PWR: | green: Fieldbus voltage > 10 V |
| LED CHANNEL ERROR: | red flashing: short-circuit |
| LED COM: | yellow: bus activity |
| LED TERM ON: | yellow: termination activated |
| Electromagnetic compatibility: Directive 2004/108/EC: | EN 61326-1:2006 |
| Electromagnetic compatibility: | NE 21:2006 |
| Degree of protection: | IEC 60529 |
| Fieldbus standard: | IEC 61158-2 |
| Shock resistance: | EN 60068-2-27 |
| Vibration resistance: | EN 60068-2-6 |
| Ambient temperature: | -40 ... 70 °C (-40 ... 158 °F) |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Relative humidity: | 95 % non-condensing |
| Shock resistance: | 15 g , 11 ms |
| Vibration resistance: | 5 g , 10 ... 150 Hz |
| Connection type: | screw fixing |
| Core cross-section: | max. 2.5 mm2 / AWG 12-24 |
| Housing material: | Polycarbonate |
| Housing width: | 216 mm |
| Housing height: | 100 mm |
| Housing depth: | 50 mm |
| Degree of protection: | IP20 |
| Mass: | 800 g |
| Mounting: | DIN rail mounting |
| Coating: | resin filled |
| EU-Type Examination Certificate: | PTB 04 ATEX 2100 X |
| Electromagnetic compatibility: Marking: | II 2 G Ex e mb IIC T4 Gb |
| Maximum values: Rated voltage: | ≤ 35 V |
| Maximum values: Prospective short-circuit current: | 100 A |
| Directive conformity: Directive 94/9/EC: | EN 60079-0:2012 , EN 60079-7:2007 , EN 60079-18:2009 |
| IECEx approval: | IECEx PTB 05.0010X |
| Directive conformity: Approved for: | Ex me II T4 |
| Marine approval: | DNV A-14038 |
| ECCN: | |
| País de origen: | SG |
| EAN: | |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |