130713
R-SP-E12
Segment Protector for Cabinet Installation
Segment Protector for Cabinet Installation, 12 increased safety outputs (Ex e), Short circuit current limitation per output, Segment Protector in Zone 1/Div. 2, Instruments in Zone 1/Div. 1, For FOUNDATION Fieldbus H1 and PROFIBUS PApa. The R SP E12 Segment Protector is a device coupler that connects field instruments to the segment. Flameproof (Ex d) field devices are connected to the trunk line via one output each. Trunk and spurs are certified increased safety (Ex e). Short-circuit protection ensures proper operation of the segment in case of unwanted faults at the spur. Work on devices always requires a hot work permit. The integrated fieldbus terminator features high-availability design and is selectable. Connectors are fixed screw terminals. Any grounding and shielding concept is possible based on FieldConnex enclosure solutions. Customizable housings host one or more Segment Protectors for different output counts.
| Design / Mounting: | Cabinet installation |
| Power dissipation: | 250 mW |
| Main cable (Trunk): Rated voltage: | 9 ... 32 V DC |
| Outputs: Number of outputs: | 12 |
| Outputs: Rated voltage: | max. 32 V |
| Outputs: Rated current: | max. 40 mA |
| Outputs: Short-circuit current: | max. 52 mA |
| Self current consumption: | max. 9 mA |
| Voltage drop main cable/outputs: | max. 1.3 V |
| Terminating resistor: | selectable 100 Ω integrated |
| Surge protection: | trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V |
| LED PWR: | green: Fieldbus voltage > 10 V |
| LED CHANNEL ERROR: | red flashing: short-circuit |
| LED COM: | yellow: bus activity |
| LED TERM ON: | yellow: termination activated |
| Electromagnetic compatibility: Directive 2004/108/EC: | EN 61326-1:2006 |
| Electromagnetic compatibility: | NE 21:2006 |
| Degree of protection: | IEC 60529 |
| Fieldbus standard: | IEC 61158-2 |
| Shock resistance: | EN 60068-2-27 |
| Vibration resistance: | EN 60068-2-6 |
| Ambient temperature: | -40 ... 70 °C (-40 ... 158 °F) |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Relative humidity: | 95 % non-condensing |
| Shock resistance: | 15 g , 11 ms |
| Vibration resistance: | 5 g , 10 ... 150 Hz |
| Connection type: | screw fixing |
| Core cross-section: | max. 2.5 mm2 / AWG 12-24 |
| Housing material: | Polycarbonate |
| Housing width: | 216 mm |
| Housing height: | 100 mm |
| Housing depth: | 50 mm |
| Degree of protection: | IP20 |
| Mass: | 800 g |
| Mounting: | DIN rail mounting |
| Coating: | resin filled |
| EU-Type Examination Certificate: | PTB 04 ATEX 2100 X |
| Electromagnetic compatibility: Marking: | II 2 G Ex e mb IIC T4 Gb |
| Maximum values: Rated voltage: | ≤ 35 V |
| Maximum values: Prospective short-circuit current: | 100 A |
| Directive conformity: Directive 94/9/EC: | EN 60079-0:2012 , EN 60079-7:2007 , EN 60079-18:2009 |
| IECEx approval: | IECEx PTB 05.0010X |
| Directive conformity: Approved for: | Ex me II T4 |
| Marine approval: | DNV A-14038 |
| ECCN: | |
| Kraj pochodzenia: | SG |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |