Pepperl+Fuchs 547054

SK-PC-D2-UU1-10-HS

Div. 2/Zone 2 Ex-Barriere SK-PC-D2-UU1-10-HS

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

The SK-PC-D2-UU1-10-HS device may be mounted in Class I, Div. 2, Groups A-D and Zone 2 IIC locations and provides Non-incendive outputs for Class I, Div 2, Groups A-D, Class II, Div 2, Groups F-G, Class III, Div 2, Zone 2 IIC, and Zone 22 IIIB areas based on the entity parameter concept. The barrier is for providing protected USB 1.1 or PS2 power and data signals to Ex-rated mouse/keyboard in the field.

Технические характеристики

Rated voltage: 9 ... 30 VDC (Um = 30 V SELV)
Input current: 120 mA nominal 500 mA max
LED ON: power - keyboard power - Mouse
Interface type: USB 1.1 or PS2
Output rated operating current: 89 mA
Output voltage: 4.8 VDC
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
RoHS: Directive 2011/65/EU (RoHS): EN 50581:2012-09
Degree of protection: IEC 60529
Protection against electrical shock: IEC 61140
Ambient temperature: -40 ... 60 °C (-40 ... 140 °F)
Relative humidity: 0 ... 95% (noncondensing)
Vibration resistance: 5 G, 58 ... 150 Hz
Impact resistance: 15 g, 11 ms
Connection type: Terminal Block
Degree of protection: IP20
Connection: Supply: terminals 13+, 14- Input: terminals 9+, 10-; 11+, 12- Output: terminals 1+, 2+, 3-, 4-; 5+, 6+, 7-, 8- (field terminal) Ground: terminals 15, 16
Mass: 120 g
Dimensions: 99 mm x 85 mm x 22.5 mm
Cable length: 4.6 m (15'): barrier to keyboard/mouse 4.6 m (15'): host pc to keyboard/mouse 6.1 m (20'): total length, host PC to keyboard/mouse
EU-type examination certificate: DEMKO 14ATEX1269806X
RoHS: Marking: II 3 G Ex nA [ic] IIC T6 Gc II 3 G Ex nA [ic IIIB] IIC T6 Gc
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
UL approval: cULus (E106378)
Directive conformity: Control drawing: 116-0337
Directive conformity: Approved for: Mountable in Class I, Division 2, Groups A, B, C, D Providing non-incendive field wiring at field terminals to Class I, Division 2, Groups A, B, C, D Class II, Division 2, Groups F, G Class III, Division 2 Temperature Class T6 Mountable in Class I, Zone 2 Providing intrinsic safety wiring at field terminals for Class I, Zone 2, Group IIC and Group IIIB hazardous locations USL: Class I, Zone 2 AEx nA [ic] IIC T6 Gc Class I, Zone 2 AEx nA [ic IIIB] IIC T6 Gc CNL: Class I, Zone 2, Ex nA [ic] IIC T6 Gc X Class I, Zone 2, Ex nA [ic IIIB] IIC T6 Gc X
IECEx approval: IECEx UL 14.0017X
Directive conformity: Approved for: Ex nA [ic] IIC T6 Gc Ex nA [ic IIIB] IIC T6 Gc
Directive conformity: Standards: IEC 60079-0:2011 (6th edition) IEC 60079-11:2011 (6th edition) IEC 60079-15:2010 (4th edition)

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m