541996
LB6108A
Digital Output with Shutdown Input
8-channel, Outputs Ex ib, Mounting in Zone 2, Class I/Div.2 or in the safe area, Module can be exchanged under voltagepa. The device features 8 independent channels. The device can be used to drive low power solenoids, sounders, or LEDs. Open and short-circuit line faults are detected. The outputs are galvanically isolated from the bus and the power supply. The outputs can be switched off via a contact. This can be used for bus-independent safety applications.
| Occupied slots: | 2 |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | backplane bus |
| Rated voltage: | 12 V DC , only in connection with the power supplies LB9*** |
| Power dissipation: | 2.35 W |
| Power consumption: | 2.35 W |
| Connection: | backplane bus |
| Interface: | manufacturer-specific bus to standard com unit |
| Number of channels: | 8 |
| Suitable field devices: Field device: | Solenoid Valve |
| Suitable field devices: Field device [2]: | audible alarm |
| Suitable field devices: Field device [3]: | visual alarm |
| Connection: | channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+, 16- |
| Current limit: | 8 mA |
| Open loop voltage: | 20 V |
| Line fault detection: | can be switched on/off for each channel via configuration tool |
| Suitable field devices: Test current: | 0.33 mA |
| Suitable field devices: Short-circuit: | < 300 Ω |
| Suitable field devices: Open-circuit: | > 50 kΩ |
| Response time: | 20 ms (depending on bus cycle time) |
| Watchdog: | within 0.5 s the device goes in safe state, e.g. after loss of communication |
| LED indication: | LED green: supply LED red: line fault , communication error red flashing |
| Coding: | optional mechanical coding via front socket |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1 |
| Electromagnetic compatibility: | NE 21 |
| Degree of protection: | IEC 60529 |
| Environmental test: | EN 60068-2-14 |
| Shock resistance: | EN 60068-2-27 |
| Vibration resistance: | EN 60068-2-6 |
| Damaging gas: | EN 60068-2-42 |
| Relative humidity: | EN 60068-2-56 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 95 % non-condensing |
| Shock resistance: | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
| Vibration resistance: | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
| Damaging gas: | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection: | IP20 when mounted on backplane |
| Connection: | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) |
| Mass: | approx. 160 g |
| Dimensions: | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) |
| EU-type examination certificate: | PTB 03 ATEX 2042 X |
| Electromagnetic compatibility: Marking: | II (2) G [Ex ib] IIC II (2) D [Ex ib] IIIC |
| Output: Voltage: | 28 V |
| Output: Current: | 13.5 mA |
| Output: Power: | 376 mW (characteristic curve rectangular type) |
| Certificate: | PF 08 CERT 1234 X |
| Output: Marking: | II 3 G Ex nA IIC T4 Gc |
| Galvanic isolation: Output/power supply, internal bus: | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 |
| ATEX approval: | PF 08 CERT 1234 X PTB 03 ATEX 2042 X |
| IECEx approval: | BVS 09.0037X |
| Directive conformity: Approved for: | Ex nA [ib Gb] IIC T4 Gc [Ex ib Db] IIIC |
| EAC approval: | Russia: RU C-IT.MIII06.B.00129 |
| Marine approval: Lloyd Register: | 15/20021 |
| Marine approval: American Bureau of Shipping: | T1450280/UN |
| Marine approval: Bureau Veritas Marine: | 22449/B0 BV |
| System information: | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. |
| Supplementary information: | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| ТН ВЭД: | |
| Страна происхождения: | DE |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |