282664
VAA-2E2A-KE1-SE
AS-Interface Sicherheitsmodul VAA-2E2A-KE1-SE
The VAA-2E2A-KE1-SE is an AS-Interface safety module with two safety-related inputs and two outputs. A self-testing electronic protective system can be connected to the two safety-related inputs. The outputs are conventional electronic outputs that can be loaded to a total of 3 A (max. 1 A per output). The housing is only 22.5 mm wide and 48.5 mm tall and takes up little space in the switch cabinet. A snap-on function mounts the module onto the 35 mm mounting strip in line with. EN 50022. An addressing socket is integrated in the module. The connection is made via plug-in terminals. A four-way (black) terminal block is used for the inputs. The AS-Interface is connected via a two-way (yellow) terminal block. Each channel has an LED mounted on the top side of the module to display the current switching status. There is an LED for monitoring AS-Interface communication and for displaying that the module has the address 0. In the event of communication faults, the outputs are disconnected from the power supply (only for P0 = 1). If a noncontact protective system is connected, the module can be upgraded to performance level e in accordance with. EN ISO 13849-1 if wired appropriately. As per the approval in accordance with. EN 62061, a Safety Integrity Level of up to SIL 3 can be reached.
| Slave type: | Safety-Slave |
| AS-Interface specification: | V3.0 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E223772 |
| Safety Integrity Level (SIL): | SIL 3 |
| Performance level (PL): | PL e |
| Category: | Cat. 4 |
| Mission Time (TM): | 20 a |
| PFHd: | 2.83 E-9 |
| PFD: | 8 E-7 |
| LED FAULT: | Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault |
| LED AS-i: | AS-Interface voltage; LED green |
| LED AUX: | auxiliary voltage UAUX ; LED green |
| LED IN: | switching state (input); 2 LED yellow |
| LED OUT: | Switching state (output); 2 LED yellow |
| Auxiliary voltage (output): | 24 V (20 VDC… 30 VDC) |
| Rated operating voltage: | 22 ... 31.6 V |
| Rated operating current: | ≤ 70 mA |
| Protection class: | III |
| Current consumption: | max. 35 mA (AS-Interface) max. 4 A (AUX) |
| Surge protection: | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) |
| Number/Type: | 2 inputs for a 2-channel active optoelectronic protective devices (AOPD) for safeguarding positions and areas of danger up to PL e in accordance with EN / ISO 13849-1 |
| Supply: | from AUX |
| Voltage: | 20 ... 30 V DC pulsed |
| Current loading capacity: | 1800 mA for power supply of external sensors from AUX |
| Switching point: | Vin> 11 V for high level, input current ≥ 2.5 mA at 15 V |
| Number/Type: | 2 conventional electronic outputs, short-circuit proof |
| Supply: | from AUX |
| Current: | 1 A per output Note derating |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61326-3-1:2008 |
| Electromagnetic compatibility: | EN 61000-6-2:2005, EN 61000-6-3:2007/A1:2011 EN 61131-2:2007 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| AS-Interface: | EN 62026-2:2013 |
| Functional safety: | EN ISO 13849-1:2008 up to PL e EN 62061:2005/A1:2013 up to SIL 3 |
| Profile: | S-7.B.1. |
| IO code: | 7 |
| ID code: | B |
| ID1 code: | F |
| ID2 code: | 1 |
| Data bits (function via AS-Interface): | input output |
| Electromagnetic compatibility: D0: | dyn. safety code 1 OUT 1 |
| Electromagnetic compatibility: D1: | dyn. safety code 1 OUT 2 |
| Electromagnetic compatibility: D2: | dyn. safety code 2 - |
| Electromagnetic compatibility: D3: | dyn. safety code 2 - |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
| Electromagnetic compatibility: P1: | not used |
| Electromagnetic compatibility: P2: | not used |
| Electromagnetic compatibility: P3: | not used |
| Ambient temperature: | 0 ... 55 °C (32 ... 131 °F) , no moisture condensation |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Altitude: | ≤ 2000 m above MSL |
| Shock and impact resistance: | ≤ 15 g at T ≤ 11 ms, 10 ... 55 Hz, 0,5 mm amplitude |
| Degree of protection: | IP20 |
| Connection: | removable terminals, terminal connection 0.2 ... 2.5 mm2 |
| Material: Housing: | PA 66-FR |
| Mass: | 60 g |
| Mounting: | DIN mounting rail |
| Tightening torque of clamping screws: | 0.5 Nm ... 0.6 Nm |
| ТН ВЭД: | |
| Страна происхождения: | DE |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |