276398
S1SD-1AI-1U.2
Isolating Amplifier
1-channel signal conditioner, 24 V DC supply, Input bipolar current and voltage sources, Output bipolar current and voltage sources, Accuracy 0.1 %, Configurable via DIP switches and potentiometer, Connection via screw terminalspa. This signal conditioner provides the galvanic isolation between field circuits and control circuits. The device has an input for bipolar current and voltage sources. At the output the signals are available as bipolar current and voltage sources. The device is easily configured by the use of DIP switches and potentiometers. The device can be powered via terminals or Power Bus.
| Signal type: | Analog input |
| Operation time: | MTBF: 490 a acc. to SN 29500 stationary continuous operating, average ambient temperature 40 °C (104 °F) |
| Connection: | Power Bus or terminals 1-, 2+ |
| Rated voltage: | 16.8 ... 31.2 V DC |
| Power dissipation: | 0.6 W |
| Power consumption: | 0.8 W |
| Connection side: | field side |
| Transmission range: | linearity range: unipolar -1 ... 110 % bipolar -110 ... 110 % |
| Input I: Connection: | terminals 5+, 6- |
| Input I: Input signal: | 0/4 ... 20 mA , 0/2 ... 10 mA , ± 10 mA, ± 20 mA , max. 50 mA |
| Input I: Input resistance: | ≤ 25 Ω |
| Input II: Connection: | terminals 7+, 8- |
| Input II: Input signal: | 0/1 ... 5 V , 0/2 ... 10 V , ± 5 V , ± 10 V , max. 30 V |
| Input II: Input resistance: | > 1 MΩ |
| Connection side: | control side |
| Connection: | terminals 3-, 4+ |
| Analog voltage output: | 0/1 ... 5 V , 0/2 ... 10 V , ± 5 V, ± 10 V , load ≥ 2 kΩ |
| Analog current output: | 0/4 ... 20 mA, ± 10 mA, ± 20 mA, load ≤ 600 Ω |
| Ripple: | ≤ 10 mV eff |
| Accuracy: | max. 0.1 % of full-scale value |
| Influence of ambient temperature: | < 100 ppm/K of full-scale value |
| Frequency range: | 0 ... 100 Hz , 0 ... 8 kHz |
| Settling time: | 7 ms , 100 µs |
| Output/power supply: | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min |
| Input/Other circuits: | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min |
| Control elements: | DIP-switch potentiometer |
| Configuration: | via DIP switches via potentiometer |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Degree of protection: | IEC 60529:2001 |
| Protection against electrical shock: | EN 61010-1:2010 |
| Ambient temperature: | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Damaging gas: | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Core cross-section: | 0.5 ... 2.5 mm2 (20 ... 14 AWG) |
| Mass: | approx. 70 g |
| Dimensions: | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Certificate: | DEMKO 16 ATEX 1750X |
| Electromagnetic compatibility: Marking: | II 3G Ex nA IIC T4 Gc |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
| UL approval: | E106378 |
| IECEx approval: | IECEx UL 16.0116X |
| Directive conformity: Approved for: | Ex nA IIC T4 Gc |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ТН ВЭД: | |
| Страна происхождения: | DE |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |