This isolated barrier is used for intrinsic safety applications. It is a HART loop converter that provides power to transmitters or can be connected to existing HART loops in parallel. 1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 2 relay contact outputs (change-over contacts), 3 analog outputs 4 mA .. 20 mA, Sink and source mode output, Configurable by keypadpa. It is able to evaluate up to four HART variables (PV, SV, TV, QV). Of those four HART variables, the data contained in any three of them can be converted to three different 4 mA .. 20 mA current signals. These loop signals can be connected to display devices or analog inputs on the process control system/ control system. In addition to the current outputs, two form C changeover relay contacts are available and can be programmed to operate at trip values from the HART variables. The unit is easily programmed by the use of a keypad located on the front of the unit or with the PACTware™ configuration software. For additional information, refer to the manual and www.pepperl-fuchs.com.

Технические характеристики

Signal type: Analog input
Connection: Power Rail or terminals 23+, 24-
Rated voltage: 19 ... 30 V DC
Rated current: approx. 130 mA at 24 V DC
Power dissipation: 2.5 W
Power consumption: 3.1 W
Conformity: HART field device input (revision 5 to 7)
Programming interface: programming socket
Connection side: field side
Connection: terminals 1, 2, 3, 4, 5, 6
Open circuit voltage/short-circuit current: typ. 24 V / 28 mA
Input resistance: 250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6)
Available voltage: ≥ 15.5 V at 20 mA, short-circuit protected
Connection side: control side
Connection: output I: terminals 10, 11, 12, output II: terminals 16, 17, 18 output III: terminals 7, 8, 9, output IV: terminals 13, 14, 15, output V: terminals 19, 20, 21
Output I, II: Output signal: relay and LED yellow
Output I, II: Mechanical life: 107 switching cycles
Output I, II: Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Output III, IV, V: Output signal: analog
Output III, IV, V: Current range: 4 ... 20 mA , (source or sink mode)
Output III, IV, V: Load: max. 650 Ω , source mode
Output III, IV, V: Voltage range: 5 ... 30 V , sink mode from external supply
Output III, IV, V: Fault signal: downscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value
Other outputs: HART communicator on terminals 22, 24
Collective error message: Power Rail and LED red
Output III, IV, V: Resolution: max. 2 µA
Output III, IV, V: Accuracy: < 20 µA, 10 µA typ.
Output III, IV, V: Influence of ambient temperature: < ± 2 µA/K
Output III, IV, V: Duration of measurement/Response delay: HART message acquisition time plus 100 ms
Relay: programmable either for fault or trip value (with direction, hysteresis and delay)
Output I/II: functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Output I, II/other circuits: reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms
Output III/IV/V/power supply: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons via PACTware
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: 300 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: BASEEFA 07 ATEX 0174
Low voltage: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC
Supply: Maximum safe voltage: 253 V AC (Attention! The rated voltage can be lower.)
Equipment: terminals 1, 4/3 (with link between terminals 4 and 5)
Supply: Voltage Uo: 25.2 V
Supply: Current Io: 104.9 mA
Supply: Power Po: 0.661 W
Equipment: terminals 2, 5/3
Supply: Voltage Ui: < 28 V
Supply: Power Pi: < 1.33 W
Supply: Voltage Uo: 1.1 V
Supply: Current Io: 11.9 mA
Supply: Power Po: 4 mW
Output I, II: terminals 10, 11, 12; 16, 17, 18 , non-intrinsically safe
Supply: Maximum safe voltage: 253 V (Attention! Um is no rated voltage.)
Supply: Contact loading: 253 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (BASEEFA 07 ATEX 0174) 50 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (Pepperl+Fuchs self-declaration)
Output III, IV, V: terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 , non-intrinsically safe
Supply: Maximum safe voltage: 253 V (Attention! Um is no rated voltage.)
Certificate: PF 07 CERT 1141 X
Supply: Marking: II 3G Ex nA nC IIC T4 Gc
Galvanic isolation: Input/Other circuits: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
FM approval: Control drawing: 116-0129
IECEx approval: IECEx certificate: IECEx BAS 07.0047
IECEx approval: IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m