Pepperl+Fuchs 261916

KFD2-HLC-Ex1.D

HART Loop Converter

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

This isolated barrier is used for intrinsic safety applications. It is a HART loop converter that provides power to transmitters or can be connected to existing HART loops in parallel. 1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 3 analog outputs 4 mA .. 20 mA, Sink and source mode output, Configurable by keypadpa. It is able to evaluate up to four HART variables (PV, SV, TV, QV). Of those four HART variables, the data contained in any three of them can be converted to three different 4 mA .. 20 mA current signals. These loop signals can be connected to display devices or analog inputs on the process control system/ control system. The unit is easily programmed by the use of a keypad located on the front of the unit or with the PACTware™ configuration software. For additional information, refer to the manual and www.pepperl-fuchs.com.

Технические характеристики

Signal type: Analog input
Connection: Power Rail or terminals 23+, 24-
Rated voltage: 19 ... 30 V DC
Rated current: approx. 120 mA at 24 V DC
Power dissipation: 2.3 W
Power consumption: 2.9 W
Conformity: HART field device input (revision 5 to 7)
Programming interface: programming socket
Connection side: field side
Connection: terminals 1, 2, 3, 4, 5, 6
Open circuit voltage/short-circuit current: typ. 24 V / 28 mA
Input resistance: 250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6)
Available voltage: ≥ 15.5 V at 20 mA, short-circuit protected
Connection side: control side
Connection: output I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21
Output signal: analog
Current range: 4 ... 20 mA , (source or sink mode)
Load: max. 650 Ω , source mode
Voltage range: 5 ... 30 V , sink mode from external supply
Fault signal: downscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value
Other outputs: HART communicator on terminals 22, 24
Collective error message: Power Rail and LED red
Output I, II, III: Resolution: max. 2 µA
Output I, II, III: Accuracy: < 20 µA, 10 µA typ.
Output I, II, III: Influence of ambient temperature: < ± 2 µA/K
Output I, II, III: Duration of measurement/Response delay: HART message acquisition time plus 100 ms
Output I/II/III/power supply: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons via PACTware
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: 300 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: BASEEFA 07 ATEX 0174
Low voltage: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC
Supply: Maximum safe voltage: 253 V AC (Attention! The rated voltage can be lower.)
Equipment: terminals 1, 4/3 (with link between terminals 4 and 5)
Supply: Voltage Uo: 25.2 V
Supply: Current Io: 104.9 mA
Supply: Power Po: 0.661 W
Equipment: terminals 2, 5/3
Supply: Voltage Ui: < 28 V
Supply: Power Pi: < 1.33 W
Supply: Voltage Uo: 1.1 V
Supply: Current Io: 11.9 mA
Supply: Power Po: 4 mW
Output I, II, III: terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 non-intrinsically safe
Supply: Maximum safe voltage: 253 V (Attention! Um is no rated voltage.)
Certificate: PF 07 CERT 1142 X
Supply: Marking: II 3G Ex nA IIC T4 Gc
Galvanic isolation: Input/Other circuits: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
FM approval: Control drawing: 116-0129
IECEx approval: IECEx certificate: IECEx BAS 07.0047
IECEx approval: IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m