Pepperl+Fuchs 255621

KFD2-CRG2-1.D

Transmitter Power Supply

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA ... 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511pa. This signal conditioner provides the galvanic isolation between field circuits and control circuits. The device supplies 2-wire and 3-wire transmitters, and can also be used with current sources. Two relays and an active 0/4 mA ... 20 mA current source are available as outputs. The relay contacts and the current output can be integrated in security-relevant circuits. The current output is easily scaled. On the display the measured value can be indicated in various physical units. The device is easily configured by the use of keypad or with the PACTware configuration software. The input has a line fault detection. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output. For additional information, refer to the manual and www.pepperl-fuchs.com.

Технические характеристики

Signal type: Analog input
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 23+, 24-
Rated voltage: 20 ... 30 V DC
Rated current: approx. 130 mA
Power dissipation: 2 W
Power consumption: 2.5 W
Programming interface: programming socket
Connection side: field side
Connection: terminals 1, 2, 3
Input I: Input signal: 0/4 ... 20 mA
Input I: Available voltage: ≥ 15 V at 20 mA
Input I: Open circuit voltage/short-circuit current: 24 V / 33 mA
Input I: Input resistance: 45 Ω (terminals 2, 3)
Input I: Line fault detection: breakage I < 0.2 mA; short-circuit I > 22 mA
Connection side: control side
Connection: output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7-
Output signal: 0 ... 20 mA or 4 ... 20 mA
Output I, II: signal, relay
Input I: Contact loading: 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Input I: Mechanical life: 5 x 107 switching cycles
Output III: Signal, analog
Input I: Current range: 0 ... 20 mA or 4 ... 20 mA
Input I: Open loop voltage: max. 24 V DC
Input I: Load: max. 650 Ω
Input I: Fault signal: downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Energized/De-energized delay: 0 ... 250 s , adjustable
Input I: Accuracy: < 30 µA
Input I: Influence of ambient temperature: 0.003 %/K (30 ppm)
Output I, II: Response delay: ≤ 200 ms at bounce from 0 ... 20 mA
Output III: Resolution: ≤ 10 µA
Output III: Accuracy: < 20 µA
Output III: Influence of ambient temperature: 0.005 %/K (50 ppm)
Output III: Reaction time: < 650 ms at bounce from 0 ... 20 mA at the input, 90 % of output full-scale value
Input/Other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, III: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply and collective error: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Interface/power supply and collective error: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons via PACTware
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: 300 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
UL approval: E223772
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03) - FDT framework PACTware 4.1 - device type manager DTM Interface Technology - adapter K-ADP-USB

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m