This isolated barrier is used for intrinsic safety applications. 1-channel isolated barrier, Universal usage at different power supplies, Thermocouple, RTD, potentiometer or voltage input, Redundant TC input, Current output 0/4 mA ... 20 mA, 2 relay contact outputs, Configurable by PACTware or keypad, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC 61508/IEC 61511pa. The device converts the signal of a resistance thermometer, thermocouple, potentiometer, or voltage source to a proportional output current. It also provides a relay trip value. The removable terminal block K-CJC-** is available as an accessory for internal cold junction compensation of thermocouples. A fault is signalized by LEDs acc. to NAMUR NE44. The device is easily configured by the use of the PACTware configuration software. For additional information, refer to the manual and www.pepperl-fuchs.com.

Технические характеристики

Signal type: Analog input
Safety Integrity Level (SIL): SIL 2
Connection: terminals 23, 24
Rated voltage: 20 ... 90 V DC / 48 ... 253 V AC
Power dissipation/power consumption: ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA
Programming interface: programming socket
Connection side: field side
Connection: terminals 1, 2, 3, 4, 6
RTD: Pt100, Pt500, Pt1000, Ni100, Ni1000
: Types of measuring: 2-, 3-, 4-wire technology
: Lead resistance: max. 50 Ω
: Measurement loop monitoring: sensor breakage, sensor short-circuit
Thermocouples: type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995)
: Cold junction compensation: external and internal
: Measurement loop monitoring: sensor breakage
Potentiometer: 0.8 ... 20 kΩ
: Types of measuring: 2-, 3-, 5-wire technology
Voltage: 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV
Input resistance: ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV)
Measuring current: approx. 400 µA with resistance measuring sensor
Connection side: control side
Connection: output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7-
Output I, II: relay
: Contact loading: 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
: Mechanical life: 5 x 107 switching cycles
: Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Output III: Analog current output
: Current range: 0 ... 20 mA or 4 ... 20 mA
: Open loop voltage: max. 24 V DC
: Load: max. 650 Ω
: Fault signal: downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Deviation: Temperature effect: Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span
Deviation: RTD: max. 0.2 % of span
Deviation: Thermocouples: max. 10µV deviation of CJC: ±0.8 K
Deviation: Voltage: 0.1 % of span
Deviation: Potentiometer: 0.1 % of span when < 5 kΩ 0.5 % of span when > 5 kΩ
Deviation: Current output: max. 20 µA
Sampling rate: approx. 700 ms
Input/Other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II against eachother: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons via PACTware
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2007
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: 300 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: TÜV 03 ATEX 2140
Low voltage: Marking: II (1)G [Ex ia] IIC , II (1)D [Ex iaD]
Low voltage: Input: Ex ia IIC, Ex iaD
Supply: Maximum safe voltage: 40 V DC (Attention! The rated voltage can be lower.)
Input: terminals 2, 6 (for active equipment)
Supply: Voltage: 13.1 V
Supply: Current: 8 mA
Supply: Power: 67 mW
Supply: Voltage: 29 V
Supply: Current: 11 mA
Supply: Power: 200 mW
Inputs: terminals 1, 2, 3, 4, 6 (for passive equipment)
Supply: Voltage Uo: 13.1 V
Supply: Current Io: 21 mA
Supply: Power Po: 67 mW
Output: Contact loading: 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 03 ATEX 2140)
Analog output: Maximum safe voltage: 40 V (Attention! The rated voltage can be lower.)
Interface: Maximum safe voltage: 40 V (Attention! The rated voltage can be lower.) , RS 232
Galvanic isolation: Input/Other circuits: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx approval: IECEx certificate: IECEx TUN 09.0019
IECEx approval: IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m