Pepperl+Fuchs 231221

KFD2-WAC2-Ex1.D

Strain Gauge Converter

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

1-channel isolated barrier, 24 V DC supply (Power Rail), Strain gauge input (full or half bridge), Output 0 mA .. ± 20 mA or 0 V .. ± 10 V, 2 relay contact outputs, Programmable high/low alarm, Configurable by PACTware or keypad, RS-485 interface, Line fault detection (LFD)pa. This isolated barrier is used for intrinsic safety applications. The device is used with strain gauges, load cells and resistance measuring bridges. Designed to provide 5 V excitation voltage, this barrier’s high quality A/D converter allows it to be used with those devices requiring 10 V. Up to four 350 Ω strain gauges connected in parallel may be powered and evaluated. The device is easily configured by the use of keypad or with the PACTware configuration software. The current measurement for tare, zero point, and final value can be entered in this manner. A fault is signalized by LEDs and a separate collective error message output. For additional information, refer to the manual and www.pepperl-fuchs.com.

Технические характеристики

Signal type: Analog input
Connection: Power Rail or terminals 23+, 24-
Rated voltage: 20 ... 35 V DC
Ripple: within the supply tolerance
Power consumption: max. 3 W
Connection: Power Rail or terminals 19+, 20 GND, 21-
Type: RS-485
Programming interface: programming socket
Connection: terminals 1+, 2-, 3+, 4-, 5+, 6-
Lead resistance: max. 25 Ω per line
Input I: Connection: terminals 1+, 2-
Sensor supply: 1 ... 5 V
Input I: Connection: terminals 3+, 4- (supply); 5+, 6- (signal)
Input I: Short-circuit current: 50 mA
Input I: Load: ≥ 116 Ω up to 5V, ≥ 85 Ω up to 4V
Connection side: field side
Connection: Input I: terminals 1+, 2-; Input II: terminals 13+, 14-; Input III: terminals 15+, 14-
Programmable Tare: 0 ... 500 % of span
Input I: Signal, analog
Input I: Input signal: -100 ... 100 mV
Input I: Input resistance: > 1 MΩ for voltage measurement
Input II, III: tare adjustment, calibration and zero
Input I: Open circuit voltage/short-circuit current: 18 V / 5 mA
Input I: Active/Passive: I > 4 mA/I < 1.5 mA
Connection side: control side
Connection: Output I: terminals 10, 11, 12; Output II: terminals 16, 17, 18; Output III: terminals 7-, 8+, 9-
Output I, II: Relay output
Input I: Contact loading: 253 V AC/2 A/500 VA/cos φ min. 0.7; 40 V DC/2 A resistive load
Input I: Mechanical life: 2 x 107 switching cycles
Output III: Analog output
Input I: Current range: -20 ... 20 mA
Input I: Load: max. 550 Ω
Input I: Analog voltage output: 0 ... ± 10 V; output resistance 500 Ω (bridge between terminal 7 and 9)
Input I: Analog current output: 0 ... ± 20 mA or 4 ... 20 mA; load 0 ... 550 Ω (terminals 7 and 8)
Line fault detection: downscale -21.5 mA (-10.75 V) or 2 mA (1 V), upscale 21.5 mA (10.75 V)
Collective error message: Power Rail
Deviation: Resolution/accuracy: ≤ ± 0.05 % incl. non-linearity and hysteresis
Deviation: Temperature effect: ≤ ± 0.01 %/K
Reaction time: 300 ... 850 ms
Input I/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II against eachother: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/Input II, III: not available
Output III/Programming socket: not available
Other circuits from each other: functional insulation, rated insulation voltage 50 Veff
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons via PACTware
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 250 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: TÜV 04 ATEX 2531
Low voltage: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Supply: Power Rail or terminals 23+, 24- non-intrinsically safe
Low voltage: Maximum safe voltage: 40 V DC (Attention! Um is no rated voltage.)
Input I: terminals 1+, 2- Ex ia IIC, Ex iaD
Low voltage: Voltage Uo: 14 V
Low voltage: Current Io: 238 mA
Low voltage: Power Po: 833 mW (linear characteristic)
Input II and III: terminals 13+, 14-; 15+, 14- non-intrinsically safe
Low voltage: Maximum safe voltage Um: 40 V DC (Attention! Um is no rated voltage.)
Output I, II: terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Low voltage: Maximum safe voltage: 253 V AC / 40 V DC (Attention! Um is no rated voltage.)
Low voltage: Contact loading: 253 V AC/2 A/500 VA/cos φ min. 0.7; 40 V DC/2 A resistive load
Output III: terminals 7-, 8+, 9- non-intrinsically safe
Low voltage: Maximum safe voltage Um: 40 V DC (Attention! Um is no rated voltage.)
Interface: RS 485 programming jack
Low voltage: Maximum safe voltage: 40 V DC (Attention! Um is no rated voltage.)
Galvanic isolation: Input I/other circuits: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012
FM approval: Control drawing: 116-0302 (cFMus)
UL approval: E223772
IECEx approval: IECEx certificate: IECEx TUN 06.0005
IECEx approval: IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-05(-S) - profile rail K-DUCT-BU(-UPR-05) - FDT framework PACTware 5.X - device type manager DTM Interface Technology - adapter K-ADP-USB

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m