Pepperl+Fuchs 231193

KFD2-UFC-1.D

Frequency Converter with Trip Values

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2- or 3-wire sensors, NAMUR sensors or dry contacts, Input frequency 1 mHz .. 10 kHz, Current output 0/4 mA ... 20 mA, Relay contact and transistor output, Start-up override, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511pa. This signal conditioner provides the isolation for non-intrinsically safe applications. The device is a universal frequency converter that changes a digital input signal into a proportional free adjustable 0/4 mA ... 20 mA analog output signal and functions as a switch amplifier and a trip alarm. The functions of the switch outputs (2 relay outputs and 1 potential free transistor output) are easily adjustable [trip value display (min/max alarm), serially switched output, pulse divider output, error signal output]. The device is easily configured by the use of keypad or with the PACTware configuration software. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output. For additional information, refer to the manual and www.pepperl-fuchs.com.

Технические характеристики

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: terminals 23+, 24- or power feed module/Power Rail
Rated voltage: 20 ... 30 V DC
Rated current: approx. 100 mA
Power dissipation/power consumption: ≤ 2 W / 2.2 W
Programming interface: programming socket
Connection side: field side
Connection: Input I: 2-wire sensor: terminals 1+, 3- three wire sensor: terminals 1+, 2- and 3 input II: terminals 13+, 14- start-up override;
Input I: 2- or 3-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
: Open circuit voltage/short-circuit current: 22 V / 40 mA
: Input resistance: 4.7 kΩ
: Switching point/switching hysteresis: logic 1: > 2.5 mA ; logic 0: < 1.9 mA
: Pulse duration: > 50 µs
: Input frequency: 0.001 ... 10000 Hz
: Line fault detection: breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Input II: startup override: 1 ... 1000 s, adjustable in steps of 1 s
: Active/Passive: I > 4 mA (for min. 100 ms) / I < 1.5 mA
: Open circuit voltage/short-circuit current: 18 V / 5 mA
Connection side: control side
Connection: output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 outout III: terminasl 19+, 20- output IV: terminals 8+, 7-
Output I, II: signal, relay
: Contact loading: 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
: Mechanical life: 5 x 107 switching cycles
: Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Output III: electronic output, passive
: Contact loading: 40 V DC
: Signal level: 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA)
Output IV: analog
: Current range: 0 ... 20 mA or 4 ... 20 mA
: Open loop voltage: max. 24 V DC
: Load: max. 650 Ω
: Fault signal: downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
Collective error message: Power Rail
Input I: Measurement range: 0.001 ... 10000 Hz
Input I: Resolution: 0.1 % of the measurement value , ≥ 0.001 Hz
Input I: Accuracy: 0.1 % of the measurement value , > 0.001 Hz
Input I: Measuring time: < 100 ms
Input I: Influence of ambient temperature: 0.003 %/K (30 ppm)
Output I, II: Response delay: ≤ 200 ms
Output IV: Resolution: < 10 µA
Output IV: Accuracy: < 20 µA
Output IV: Influence of ambient temperature: 0.005 %/K (50 ppm)
Input I/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, III: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply and collective error: basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III/IV: basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output IV/power supply and collective error: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Start-up override/power supply and collective error: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Interface/power supply and collective error: functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Interface/output III: basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Display elements: LEDs , display
Control elements: Control panel
Configuration: via operating buttons via PACTware
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: 300 g
Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
Certificate: PF 08 CERT 1216 X
Low voltage: Marking: II 3G Ex nA nC IIC T4 Gc
Output I, II: Contact loading: 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Ambient conditions: Ambient temperature: -20 ... 50 °C (-4 ... 122 °F)
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-15:2010
UL approval: E223772
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m