229182
VAA-2E1A-G10-SAJ/EA2J-1M
AS-Interface Sicherheitsmodul VAA-2E1A-G10-SAJ/EA2J-1M
The VAA-2E1A-G10-SAJ/EA2J- * is an AS-Interface safety module with 2 safety-related inputs and one conventional output. A two-channel mechanical switch or a single channel mechanical switch each can be connected to the two safety-related inputs. The output is a conventional electronic non-safety-related output, which can be loaded with 50 mA. The module is suitable for remote connection of switches in very limited space. The onepiece housing provides a degree of protection of IP67. The connection to the AS-Interface cable is achieved by means of insulation piercing method of the inserted flat cables. The inputs and the output are connected via open cable ends. To display the current switching state, there is a LED for each channel mounted on top of the module. A LED indicating the AS-Interface communication and the adress 0 of the module is also available. If a communication error occurs, the outputs are switched off (only at P0 = 1). The module can be used up to Category 4/PL e according to ISO 13849-1, SIL 3 according to EN 62061. If two single-channel switches are connected, the module can be used up to Category 2/ PL c according to ISO 13849-1, SIL 1 according to EN 62061.
| Slave type: | Safety-Slave |
| AS-Interface specification: | V3.0 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E223772 "For use in NFPA 79 Applications only" |
| LED FLT: | error display; LED red red: communication error or address is 0 |
| LED AS-i: | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
| LED IN: | switching state (input); 2 LED yellow |
| LED OUT: | Switching state (output); LED yellow |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface (PELV) |
| Rated operating current: | ≤ 90 mA |
| Protection class: | III |
| Surge protection: | overvoltage category III |
| Rated insulation voltage: | 32 V |
| Pulse withstand voltage: | 0.8 kV |
| Number/Type: | 2 safety-related inputs for mechanical contacts, crossed-circuit monitored: 2 single-channel contacts: up to category 2/PL c to ISO 13849-1 or 1 2-channel contact: up to category 4/PL e to ISO 13849-1 |
| Supply: | from AS-Interface |
| Voltage: | 20 ... 30 V DC pulsed |
| Current: | input current limited ≤ 15 mA, short-circuit protected |
| Number/Type: | 1 conventional electronic output, PNP |
| Supply: | from AS-Interface |
| Voltage: | (UASI - 7.0 V) ≤ UOUT ≤ UASI |
| Current: | 50 mA , short-circuit/overload protected |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61000-6-2:2005 EN 61000-6-4:2007 |
| Machinery Directive: Directive 2006/42/EC: | EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Electrical safety: | IEC 61140:2009 |
| Emitted interference: | EN 61000-6-4:2007 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | IEC 62026-2:2013 EN 62061:2005 EN 61000-6-2:2005 |
| Functional safety: | EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 |
| Profile: | S-7.B |
| IO code: | 7 |
| ID code: | B |
| ID1 code: | F |
| ID2 code: | 0 |
| Data bits (function via AS-Interface): | input output |
| Machinery Directive: D0: | dyn. safety code 1 OUT 1 |
| Machinery Directive: D1: | dyn. safety code 1 - |
| Machinery Directive: D2: | dyn. safety code 2 - |
| Machinery Directive: D3: | dyn. safety code 2 - |
| Parameter bits (programmable via AS-i): | function |
| Machinery Directive: P0: | communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
| Machinery Directive: P1: | not used |
| Machinery Directive: P2: | not used |
| Machinery Directive: P3: | not used |
| UL approval: | cULus Listed, Type 1 enclosure |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature: | -25 ... 80 °C (-13 ... 176 °F) |
| Relative humidity: | < 95 % |
| Altitude: | ≤ 2000 m above MSL |
| Shock and impact resistance: | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
| Vibration resistance: | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Pollution degree: | 3 |
| Degree of protection: | IP67 This protection class is achieved by using the AS-Interface flat cable VAZ-FK-S-YE |
| Connection: | AS-Interface: AS-Interface flat cable Inputs/outputs: open conductor ends |
| Material: Contacts: | open conductor ends with connector sleeves |
| Material: Housing: | PBT |
| Material: Cable: | PUR |
| Material: Mounting screw: | Stainless steel 1.4305 / AISI 303 |
| Cable: Sheath diameter: | ∅4.8 mm |
| Cable: Bending radius: | > 8 x cable diameter, fixed > 10 x cable diameter, moving not appropriate for conveyor chains |
| Cable: Color: | black |
| Cable: Cores: | 6 x 0.25 mm2 |
| Cable: Length: | 1 m |
| Mass: | 200 g |
| Tightening torque, fastening screws: | 1.65 Nm |
| ТН ВЭД: | |
| Страна происхождения: | SG |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |