220200
HiC2077
Resistance Repeater
1-channel isolated barrier, 24 V DC supply, Resistance and RTD input (Pt100, Pt500, Pt1000), Resistance output, Accuracy 0.1 %, Line fault detection (LFD) for Pt100, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the control systempa. This isolated barrier is used for intrinsic safety applications. It transfers resistance values of RTDs or potentiometers from hazardous areas to safe areas. A 2-, 3-, or 4-wire technique is available depending on the required accuracy. The input card of the control system measures the same load as if it were connected directly to the resistance in a hazardous area.
| Signal type: | Analog input |
| Connection: | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Rated voltage: | 20 ... 30 V DC bus powered via Termination Board |
| Ripple: | within the supply tolerance |
| Rated current: | < 20 mA |
| Power consumption: | 0.35 W (24 V and 1 mA sense current) |
| Connection side: | field side |
| Connection: | SL2: 5a(+), 1a(+), 1b(-), 5b(-) |
| Line fault detection: | at Pt100 |
| Lead resistance: | ≤ 10 % of resistance value |
| Transmission range: | 0 ... 10 mA |
| Available voltage: | 9 V |
| Line fault detection: | 8 nA |
| Connection side: | control side |
| Connection: | SL1: 8a(+), 10a(+), 7a(-), 9a(-) |
| Current: | 0 ... 10 mA |
| Available voltage: | 0 ... 4.2 V |
| Fault signal: | < 18 Ω or > 400 Ω, depending on lead disconnected (measuring current ≤ 1mA) |
| Accuracy: | < ± 0.1 % of full-scale value |
| Deviation: | Im ≥ 1 mA: ±0.1 % of Rm or ± 0.1 Ω (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 Ω (the larger value is applicable). |
| : Influence of ambient temperature: | Im ≥ 1 mA, Rm ≥ 100 Ω : 0.01 %/K in the range -20 ... +60 °C (253 ... 333 K) Im < 1 mA or Rm < 100 Ω: temperature stability reduces in proportion to Im or Rm |
| Rise time: | signal response time ≤ 2 ms (10 ... 90 %) response to application of Im: Rm > 50 Ω and Im < 5mA: < 5ms response to application of Im: Rm > 30 Ω and Im < 5mA: < 10ms response to application of Im: Rm > 18 Ω and Im < 5mA: < 20ms |
| Output/power supply: | functional insulation, rated insulation voltage 50 V AC |
| Display elements: | LED |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2006 For further information see system description. |
| Degree of protection: | IEC 60529 |
| Protection against electrical shock: | UL 61010-1 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Mass: | approx. 100 g |
| Dimensions: | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
| Mounting: | on Termination Board |
| Coding: | pin 1, 3 and 4 trimmed For further information see system description. |
| EU-type examination certificate: | BASEEFA 10 ATEX 0263X |
| Electromagnetic compatibility: Marking: | II (1)GD, I (M1), [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2] |
| Electromagnetic compatibility: Voltage: | 12.4 V |
| Electromagnetic compatibility: Current: | 17.4 mA |
| Electromagnetic compatibility: Power: | 54 mW |
| Supply: Maximum safe voltage: | 253 V (Attention! The rated voltage can be lower.) |
| Output: Maximum safe voltage: | 253 V (Attention! The rated voltage can be lower.) |
| Certificate: | BASEEFA 10 ATEX 0264X |
| Output: Marking: | II 3G Ex nA II T4 |
| Galvanic isolation: Input/Output: | safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply: | safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| UL approval: Control drawing: | 116-0333 (cULus) |
| IECEx approval: | IECEx BAS 10.0122X IECEx BAS 10.0123X |
| UL approval: Approved for: | [Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I Ex nA II T4 |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ТН ВЭД: | |
| Страна происхождения: | SG |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |