Pepperl+Fuchs 220087

FB4202B2

HART Output Isolator

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

The device drives positioners, proportional valves, I/P converters, or local indicators. 1-channel, Output Ex ia, Installation in suitable enclosures in Zone 1, Module can be exchanged under voltage (hot swap)pa. Open and short-circuit line faults are detected. The output is galvanically isolated from the bus and the power supply.

Технические характеристики

Occupied slots: 1
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies FB92**
Power dissipation: 0.8 W
Power consumption: 0.95 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 1
Suitable field devices: Field device: Proportional Valve
Suitable field devices: Field device [2]: I/P converters
Suitable field devices: Field device [3]: on-site display
Connection: channel I: 2/3+, 4/5-
Current: 0 ... 25 mA short-circuit protected
Line fault detection: can be switched on/off for each channel via configuration tool , configurable via configuration tool
Suitable field devices: Short-circuit: No
Suitable field devices: Open-circuit: deviation of preset output value > 0.5 mA
Load: 750 Ω max.
HART communication: yes
HART secondary variable: MODBUS: yes; all other bus systems: no
Watchdog: within 0.5 s the device goes in safe state, e.g. after loss of communication
Deviation: After calibration: 0.1 % of the signal range at 20 °C (68 °F)
Deviation: Influence of ambient temperature: 0.1 %/10 K of the signal range
Refresh time: 100 ms
LED indication: Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit)
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2006
Electromagnetic compatibility: NE 21:2007
Degree of protection: IEC 60529:2000
Environmental test: EN 60068-2-14:2009
Shock resistance: EN 60068-2-27:2009
Vibration resistance: EN 60068-2-6:2008
Damaging gas: EN 60068-2-42:2003
Relative humidity: EN 60068-2-78:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 (module) , a separate housing is required acc. to the system description
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 350 g
Dimensions: 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
EU-type examination certificate: BVS 12 ATEX E 015 X
Electromagnetic compatibility: Marking: II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC
Output: Voltage: 27 V
Output: Current: 87 mA
Output: Power: 575 mW (linear characteristic)
Galvanic isolation: Output/power supply, internal bus: safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007
ATEX approval: BVS 12 ATEX E 015 X
INMETRO approval: Brazil: TÜV 14.1595X
EAC approval: Russia: RU C-IT.MIII06.B.00129
Marine approval: Lloyd Register: 15/20021
Marine approval: American Bureau of Shipping: T1450280/UN
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Логистические характеристики

ТН ВЭД:
Страна происхождения: Deutschland
EAN: 4050143062010
Вес: 0,49 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m