216568
KFD2-RCI-Ex1
Solenoid Driver
1-channel isolated barrier, 24 V DC supply (Power Rail), Output 20.4 mA at 13.5 V DC, 19 V DC .. 30 V DC input, Line fault detection (LFD), Conformal coating, Up to SIL 3 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. The device can be used in shut down applications with HART positioners. Via the logic input the positioner is energized or de-energized (shut down). Independent of the status, a second input enables HART communication with the positioner. With this the asset management system can request for example diagnostic information or can initiate a partial stroke test. The HART communication also works with deenergized positioner. A unique collective error messaging feature is available when used with the Power Rail system.
| Signal type: | Digital Output |
| Safety Integrity Level (SIL): | SIL 3 |
| Connection: | Power Rail or terminals 14+, 15- |
| Rated voltage: | 19 ... 30 V DC |
| Rated current: | < 35 mA |
| Power consumption: | < 0.8 W |
| Connection side: | control side |
| Connection: | terminals 10+, 11- |
| Input current: | 40 mA at 19 ... 30 V DC |
| Signal level: | 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC |
| Power consumption: | < 1.2 W |
| Operating mode: | loop powered |
| Connection side: | field side/control side |
| Output I: Connection: | terminals 1+, 3- (terminals 1+, 2 for test loop) |
| Output I: Current: | max. 20.4 mA |
| Output I: Voltage: | min. 13.5 V |
| Output I: Current: | 1-signal: 20.4 mA 0-signal: 4.2 mA |
| Output I: Voltage: | 1-signal: > 13.5 V |
| Output I: Load: | max. 650 Ω |
| Output I: Response time: | < 40 ms input to output |
| Output I: Line fault detection: | short circuit voltage < 1 V , open circuit voltage > 16 V |
| Output II: Connection: | terminal 7: source (-) or sink (+), terminal 8: source (+), terminal 9: sink (-) |
| Output II: Current: | 11 mA (source or sink mode) |
| Output II: Voltage: | 9 ... 30 V sink mode from external supply |
| Output II: Load: | max. 650 Ω , source mode , for HART ≥ 230 Ω |
| Output II: Communication: | pass-through of HART signal between input II and output |
| Input/power supply: | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| Output II/power supply: | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2012 |
| Degree of protection: | IEC 60529:2001 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Mass: | approx. 150 g |
| Dimensions: | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-Type Examination Certificate: | CESI 09 ATEX 037 |
| Electromagnetic compatibility: Marking: | II (1)GD [Ex ia] IIC; [Ex iaD] [circuit(s) in zone 0/1/2/20/21/22] |
| Electromagnetic compatibility: Equipment: | terminals 1+, 2 / 3- |
| Electromagnetic compatibility: Voltage: | 25.4 V |
| Electromagnetic compatibility: Current: | 93.6 mA |
| Electromagnetic compatibility: Power: | 595 mW (linear characteristic) |
| Supply: Maximum safe voltage: | 253 V (Attention! The rated voltage can be lower.) |
| Input: Maximum safe voltage: | 253 V (Attention! The rated voltage can be lower.) |
| Collective error message: Maximum safe voltage: | 253 V (Attention! The rated voltage can be lower.) |
| Certificate: | PF 09 CERT 1438 X |
| Collective error message: Marking: | II 3G Ex nA IIC T4 Gc |
| Galvanic isolation: Output I/other circuits: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| CSA approval: Control drawing: | 116-0335 |
| IECEx approval: IECEx certificate: | IECEx CES 09.0008 |
| IECEx approval: IECEx marking: | [Ex ia] IIC , [Ex iaD] |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Optional accessories: | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
| ТН ВЭД: | |
| Страна происхождения: | SG |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |