Pepperl+Fuchs 214233

HiC2841

Switch Amplifier

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

1-channel isolated barrier, 24 V DC supply (bus powered), Dry contact or NAMUR input, Usable as signal splitter (1 input and 2 outputs), 2 passive transistor outputs, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. The proximity sensor or switch controls two passive transistors for the safe area load. Both transistor outputs are isolated from each other and isolated from the power supply. The mode of operation can be reversed using switch S1. Switch S3 allows output II to be switched between a signal output and an error message output. Switch S2 enables or disables line fault detection of the field circuit. During an error condition, the transistors revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44. A separate output bus is available. The fault conditions can be monitored via a Fault Indication Board. This module mounts on a HiC Termination Board.

Технические характеристики

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage: 19 ... 30 V DC bus powered via Termination Board
Ripple: ≤ 10 %
Rated current: ≤ 25 mA
Power dissipation: ≤ 500 mW
Power consumption: ≤ 600 mW
Connection side: field side
Connection: SL2: 5a(+), 5b(-)
Rated values: acc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit current: approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection: breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio: min. 100 µs / min. 100 µs
Connection side: control side
Connection: SL1: 8a(+), 7a(-); 10a(+), 9a(-)
Rated voltage: 30 V DC
Rated current: 50 mA
Response time: ≤ 200 µs
Signal level: 1-signal: (external voltage) - 1 V max. for 50 mA (Tamb = 25 °C (77 °F)) 0-signal: blocked output (off-state current ≤ 10 µA)
Output I: signal ; Transistor
Output II: signal or error message ; Transistor
Connection: SL1: 6b
Output type: open collector transistor (internal fault bus)
Switching frequency: ≤ 5 kHz
Output/power supply: basic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Output/Output: basic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Galvanic isolation: EN 50178:1997
Electromagnetic compatibility: NE 21:2006 For further information see system description.
Degree of protection: IEC 60529
Protection against electrical shock: IEC 61140
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Relative humidity: ≤ 90 % , non-condensing
Degree of protection: IP20
Mass: approx. 100 g
Dimensions: 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mounting: on Termination Board
Coding: pin 1 and 2 trimmed For further information see system description.
EU-type examination certificate: BVS 09 ATEX E 157
Electromagnetic compatibility: Marking: II (1)GD [Ex ia] IIC, [Ex iaD] [circuit(s) in zone 0/1/2/20/21/22] I (M1) [Ex ia] I
Electromagnetic compatibility: Input: Ex ia, Ex iaD
Electromagnetic compatibility: Voltage: 10.5 V
Electromagnetic compatibility: Current: 17.1 mA
Electromagnetic compatibility: Power: 45 mW (linear characteristic)
Supply: Maximum safe voltage: 253 V AC (Attention! Um is no rated voltage.)
Output: Maximum safe voltage: 253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000
UL approval: Control drawing: 116-0331
IECEx approval: IECEx BVS 09.0060
UL approval: Approved for: [Ex ia Ga] IIC, [Ex ia] I , [Ex iaD]
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m