209357
FC-GPCD-SDI16-PF
Termination Board
System board for Honeywell Safety Manager, For 16-channel DI card SDI-1624, For 8 modules, Recommended module: HiC2822 (DI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: SiC plug, 20-pinpa. Termination Boards are made to carry isolated barriers and provide terminal connection for wiring. The termination board and the isolated barriers build the connection between field and system level. System connectors are synchronized to the requirements of the I/O cards used in the particular automation system. They ensure fast and reliable connection. Information about missing supply voltage of the interface modules is available for the system as potential free relay contact. Line faults from field will be reported via the same relay contact if the interface module supports this function. The Termination Boards are supplied with a robust glass fibre reinforced plastic housing as standard. This design permits the fast and reliable installation in the switch cabinet.
| Connection: | terminal block TB3 (1-, 2+; 3-, 4+) |
| Nominal voltage: | 24 V DC , in consideration of rated voltage of used isolators |
| Voltage drop: | 0.9 V , voltage drop across the series diode on the termination board must be considered |
| Ripple: | ≤ 10 % |
| Fusing: | 2 A |
| Power dissipation: | ≤ 500 mW , without modules |
| Reverse polarity protection: | yes |
| Supply: | Redundancy available. The supply for the isolators is decoupled, monitored and fused. |
| Output type: | volt-free contact |
| Contact loading: | 30 V DC , 1 A |
| Display elements: | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED LED Fault (fault indication), green LED |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2017 For further information see system description. |
| Degree of protection: | IEC 60529:2001 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature: | -40 ... 70 °C (-40 ... 158 °F) |
| Degree of protection: | IP20 |
| Connection: Field side: | explosion hazardous area: pluggable screw terminals , blue |
| Connection: Control side: | non-explosion hazardous area: SiC plug, 20-pin |
| Connection: Supply: | pluggable screw terminals , black |
| Connection: Fault output: | pluggable screw terminals , black |
| Core cross-section: | screw terminals: 0.25 ... 2.5 mm2 (24 ... 12 AWG) |
| Material: | housing: polycarbonate |
| Mass: | approx. 460 g |
| Dimensions: | 159 x 155 x 153 mm (L x W x H) , height including module assembly |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-Type Examination Certificate: | CESI 06 ATEX 022 |
| Connection: Marking: | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Non-hazardous area: Maximum safe voltage: | 250 V (Attention! Um is no rated voltage.) |
| Galvanic isolation: Field circuit/control circuit: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 |
| UL approval: Control drawing: | 116-0327 |
| IECEx approval: IECEx certificate: | IECEx CES 06.0003 |
| IECEx approval: IECEx marking: | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Designation: | provided accessory: Label Carrier HiALC-HI*TF-SET-1** |
| ТН ВЭД: | |
| Страна происхождения: | Singapur |
| EAN: | 4050143061495 |
| Вес: | 0,64 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |