Pepperl+Fuchs 202520

RLK28-FC-55-Z/31/116

Fire protection retroreflective sensor

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

It is essential that fire is not allowed to spread in buildings should it break out. Fire protection regulations therefore prescribe fire barriers. These include fire doors, industrial fire doors and fire dampers, which are generally kept closed at all times. In areas where doors are left open, such as heavily traveled passageways and corridors, a self-closing mechanism must be automatically triggered in case of fire. However, the door must not close when persons or objects are in the closing area. Legislation consequently requires monitoring with appropriate safety devices. The technical challenge is to ignore the smoke and at the same time reliably detect objects in it. These certified photoelectric sensors fulfill this function. Compact fire protection photoelectric sensor for safety devices on fire barriers, Approval in accordance with VdS Test Report FSA and externally monitored manufacture (Ü Symbol), Not sensitive to ambient light, even with switched energy saving lamps, Housing: Plastic ABS, Light type: modulated visible red light , 660 nm, Operating voltage: 12 .. 240 V AC/DC, Signal output: Relay, 1 alternator, Degree of protection: IP67fa

Технические характеристики

Effective detection range: 1 ... 3 m
Reflector distance: 1 ... 3 m
Threshold detection range: 3 m
Reference target: reflector C110-2
Light source: LED
Light type: modulated visible red light , 660 nm
Diameter of the light spot: approx. 50 mm at a distance of 3 m
Angle of divergence: emitter 1.2° receiver 2°
Ambient light limit: 80000 Lux
Accessories provided: reflector C110-2 Bracket
MTTFd: 600 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
Operation indicator: LED green
Function indicator: 2 LEDs yellow, light up when light beam is free, flash when falling short of the stability control, off when light beam is interrupted
Control elements: Time adjuster , Light-on/dark-on changeover switch
Operating voltage: 12 ... 240 V AC/DC
Power consumption: ≤ 3.5 VA
Switching type: light/dark on, switchable (selectable, light/dark switching is only activated if the receiver has 'dark on' selected.)
Signal output: Relay, 1 alternator
Switching voltage: max. 250 V AC/DC
Switching current: max. 2 A
Switching power: DC: max. 50 W AC: max. 500 VA
Switching frequency: 25 Hz
Response time: 20 ms
Timer function: ON delay (GAN), OFF delay (GAB), one shot (IAB), ON delay-one shot (GAN-IAB), ON delay-OFF delay (GAN-GAB), programmable adjustment interval 0.1 ... 10 s
Standards: EN 60947-5-2 smoke insensitive up to 2 dB/m ( EN 54-12 )
EAC conformity: TR CU 020/2011 TR CU 004/2011
Protection class: II, rated insulation voltage ≤ 250 V AC with pollution degree 1-2 according to IEC 60664-1 Output circuit insulated from control circuit in accordance with IEC 61140. Caution! The protection class 2 is only valid when the terminal compartment is closed.
CCC approval: Certified by China Compulsory Certification (CCC)
Approvals: VdS/DIBt certificate of compliance No. 25022
Ambient temperature: -40 ... 60 °C (-40 ... 140 °F)
Storage temperature: -40 ... 75 °C (-40 ... 167 °F)
Relative humidity: 30% ... 85%   non-condensing ; Non-icing
Degree of protection: IP67
Connection: terminal compartment with 8 spring-loaded terminals for wire cross section 0.5 ... 1.5 mm2, insulation stripping 7.5 ... 8.5 mm, M16 x 1.5 cable gland
Material: Housing: Plastic ABS
Material: Optical face: Plastic pane
Mass: 112 g

Логистические характеристики

ТН ВЭД:
Страна происхождения: VN
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m