188849
VAA-4E4A-G16-ZEJ/E2L
AS-Interface sensor/actuator module
G16 compact module 4 inputs (PNP) and 4 electronic outputsfa. The VAA-4E4A-G16-ZEJ/E2L is an AS-Interface compact module with 4 inputs and 4 outputs. 2- and 3-wire sensors as well as mechanical contacts can be connected to the plus switching electronic inputs. The outputs are electronic outputs which can be energized with max. 1 A per output. The particularly slim design with 30 mm is ideally suited for the common profile widths with simple sliding block mounting or screw fitting in narrow shafts. To guarantee the protection category the electronics is compound-filled. All module connections are implemented with metal inserts for high stability. The connection to the AS-Interface cable and to the external power supply is achieved via a M12 x 1 circular connector with SPEEDCON quick locking option. The advantage of the plug-connection is that no separate base is required. For addressing a standard cable with M12 x 1 screw connections can also be used. The connections to the sensors/actuators are made via M8 x 1 screw connections. The inputs and the connected sensors are supplied from the internal power supply of the module (from AS-Interface), the outputs and the connected actuators via an external power source (AUX). To indicate the current switching state there is an LED for each channel fitted to the top of the module. The outputs are protected against overload and short circuit, an output overload is indicated via an LED per channel. An LED to indicate the AS-Interface voltage, to monitor the AS-Interface communication, and to indicate that the module has an address of 0, is also available. Another LED indicates the external power supply (AUX). The module can be fitted in any position using two screws. An output overload is reported to the AS-Interface master via the function "periphery fault". The communcation with the AS-Interface remains intact.
| Slave type: | Standard slave |
| AS-Interface specification: | V3.0 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E223772 |
| MTTFd: | 190 a |
| Mission Time (TM): | 20 a |
| Diagnostic Coverage (DC): | 0 % |
| LED PWR/FAULT: | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply or output overload |
| LED AUX: | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| LED IN: | switching state (input); 4 LED yellow |
| LED OUT: | Switching status (output); 4 yellow/red LEDs Yellow: output active Red: output overload |
| Auxiliary voltage (output): | 20 ... 30 V DC PELV |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 40 mA (without sensors) / max. 240 mA |
| Protection class: | III |
| Surge protection: | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
| Number/Type: | 4 inputs for 2- or 3-wire sensors (PNP), DC |
| Supply: | from AS-Interface |
| Voltage: | 21 ... 31 V |
| Current loading capacity: | ≤ 200 mA (TB ≤ 40 °C), ≤ 150 mA (TB ≤ 70 °C), overload-proof and short-circuit protected |
| Input current: | ≤ 9 mA (limited internally) |
| Switching point: | according to DIN EN 61131-2 (Type 2) |
| : 0 (unattenuated): | ≤ 3 mA |
| : 1 (attenuated): | ≥ 5 mA |
| Signal delay: | < 1 ms (input/AS-Interface) |
| Number/Type: | 4 electronic outputs, PNP, overload and short-circuit proof |
| Supply: | from external auxiliary voltage UAUX |
| Current: | 1 A per output |
| Voltage: | ≥ (UAUX - 0.5 V) |
| Usage category: | DC-13 |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Input: | EN 61131-2 |
| Emitted interference: | EN 61000-6-4:2007 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61000-6-2:2005 EN 62026-2:2013 |
| Profile: | S-7.0 |
| IO code: | 7 |
| ID code: | 0 |
| ID1 code: | F |
| ID2 code: | E |
| Data bits (function via AS-Interface): | input output |
| Electromagnetic compatibility: D0: | IN1 OUT1 |
| Electromagnetic compatibility: D1: | IN2 OUT2 |
| Electromagnetic compatibility: D2: | IN3 OUT3 |
| Electromagnetic compatibility: D3: | IN4 OUT4 |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
| Electromagnetic compatibility: P1: | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
| Electromagnetic compatibility: P2: | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
| Electromagnetic compatibility: P3: | not used |
| Ambient temperature: | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 85 % , noncondensing |
| Climatic conditions: | For indoor use only |
| Altitude: | ≤ 2000 m above MSL |
| Shock and impact resistance: | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
| Vibration resistance: | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Pollution degree: | 3 |
| Degree of protection: | IP67 / IP68 / IP69k |
| Connection: | AS-Interface and auxiliary voltage: M12 x 1 round connector sensors/actuators: M8 x 1 round connector |
| Material: Housing: | PBT |
| Mass: | 150 g |
| Tightening torque, cable gland: | 0.4 Nm (M12 connector), 0.2 Nm (M8 connector) |
| Mounting: | screw mounting |
| ТН ВЭД: | |
| Страна происхождения: | ID |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |