Pepperl+Fuchs 188849

VAA-4E4A-G16-ZEJ/E2L

AS-Interface sensor/actuator module

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

G16 compact module 4 inputs (PNP) and 4 electronic outputsfa. The VAA-4E4A-G16-ZEJ/E2L is an AS-Interface compact module with 4 inputs and 4 outputs. 2- and 3-wire sensors as well as mechanical contacts can be connected to the plus switching electronic inputs. The outputs are electronic outputs which can be energized with max. 1 A per output. The particularly slim design with 30 mm is ideally suited for the common profile widths with simple sliding block mounting or screw fitting in narrow shafts. To guarantee the protection category the electronics is compound-filled. All module connections are implemented with metal inserts for high stability. The connection to the AS-Interface cable and to the external power supply is achieved via a M12 x 1 circular connector with SPEEDCON quick locking option. The advantage of the plug-connection is that no separate base is required. For addressing a standard cable with M12 x 1 screw connections can also be used. The connections to the sensors/actuators are made via M8 x 1 screw connections. The inputs and the connected sensors are supplied from the internal power supply of the module (from AS-Interface), the outputs and the connected actuators via an external power source (AUX). To indicate the current switching state there is an LED for each channel fitted to the top of the module. The outputs are protected against overload and short circuit, an output overload is indicated via an LED per channel. An LED to indicate the AS-Interface voltage, to monitor the AS-Interface communication, and to indicate that the module has an address of 0, is also available. Another LED indicates the external power supply (AUX). The module can be fitted in any position using two screws. An output overload is reported to the AS-Interface master via the function "periphery fault". The communcation with the AS-Interface remains intact.

Технические характеристики

Slave type: Standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
MTTFd: 190 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED PWR/FAULT: Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply or output overload
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED IN: switching state (input); 4 LED yellow
LED OUT: Switching status (output); 4 yellow/red LEDs Yellow: output active Red: output overload
Auxiliary voltage (output): 20 ... 30 V DC PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 40 mA (without sensors) / max. 240 mA
Protection class: III
Surge protection: UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Number/Type: 4 inputs for 2- or 3-wire sensors (PNP), DC
Supply: from AS-Interface
Voltage: 21 ... 31 V
Current loading capacity: ≤ 200 mA (TB ≤ 40 °C), ≤ 150 mA (TB ≤ 70 °C), overload-proof and short-circuit protected
Input current: ≤ 9 mA (limited internally)
Switching point: according to DIN EN 61131-2 (Type 2)
: 0 (unattenuated): ≤ 3 mA
: 1 (attenuated): ≥ 5 mA
Signal delay: < 1 ms (input/AS-Interface)
Number/Type: 4 electronic outputs, PNP, overload and short-circuit proof
Supply: from external auxiliary voltage UAUX
Current: 1 A per output
Voltage: ≥ (UAUX - 0.5 V)
Usage category: DC-13
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Input: EN 61131-2
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005 EN 62026-2:2013
Profile: S-7.0
IO code: 7
ID code: 0
ID1 code: F
ID2 code: E
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1 OUT1
Electromagnetic compatibility: D1: IN2 OUT2
Electromagnetic compatibility: D2: IN3 OUT3
Electromagnetic compatibility: D3: IN4 OUT4
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
Electromagnetic compatibility: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Electromagnetic compatibility: P2: Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Shock and impact resistance: 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance: 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree: 3
Degree of protection: IP67 / IP68 / IP69k
Connection: AS-Interface and auxiliary voltage: M12 x 1 round connector sensors/actuators: M8 x 1 round connector
Material: Housing: PBT
Mass: 150 g
Tightening torque, cable gland: 0.4 Nm (M12 connector), 0.2 Nm (M8 connector)
Mounting: screw mounting

Логистические характеристики

ТН ВЭД:
Страна происхождения: ID
EAN:
Вес: 0,00 kg
Длина: 0,00 m