181284
KFD2-SR2-Ex2.2S
Switch Amplifier
2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), 2 x 2 relay contact outputs with AND logic, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. Each sensor or switch controls two form A normally open relay contacts for the safe area load. The normal output state can be reversed using switches S1 and S2. Switch S3 is used to enable or disable line fault detection of the field circuit. During an error condition, the relays revert to their de-energized state and the LEDs indicate the fault according to NAMUR NE44. A unique collective error messaging feature is available when used with the Power Rail system.
| Signal type: | Digital Input |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | Power Rail or terminals 14+, 15- |
| Rated voltage: | 20 ... 30 V DC |
| Ripple: | ≤ 10 % |
| Rated current: | ≤ 50 mA |
| Power dissipation: | 1 W |
| Power consumption: | < 1.3 W |
| Connection side: | field side |
| Connection: | terminals 1+, 2+, 3-; 4+, 5+, 6- |
| Rated values: | acc. to EN 60947-5-6 (NAMUR) |
| Open circuit voltage/short-circuit current: | approx. 8 V DC / approx. 8 mA |
| Switching point/switching hysteresis: | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection: | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
| Pulse/Pause ratio: | min. 20 ms / min. 20 ms |
| Connection side: | control side |
| Connection: | output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12 |
| Output I, II, III, IV: | channel 1, 2; relay |
| Contact loading: | 50 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive load |
| Minimum switch current: | 1 mA / 24 V DC |
| Energized/De-energized delay: | approx. 20 ms / approx. 20 ms |
| Mechanical life: | 108 switching cycles |
| Collective error message: | Power Rail |
| Switching frequency: | ≤ 10 Hz |
| Input/Output: | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply: | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/power supply: | basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff |
| Output/Output: | basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Low voltage: Directive 2014/35/EU: | EN 61010-1:2010 |
| Electromagnetic compatibility: | NE 21:2004 |
| Degree of protection: | IEC 60529:2001 |
| Input: | EN 60947-5-6:2000 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Mass: | approx. 150 g |
| Dimensions: | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate: | PTB 00 ATEX 2083 |
| Low voltage: Marking: | II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2] |
| Low voltage: Input: | EEx ia IIC |
| Low voltage: Voltage: | 10.5 V |
| Low voltage: Current: | 13 mA |
| Low voltage: Power: | 34 mW (linear characteristic) |
| Supply: Maximum safe voltage: | 253 V AC / 125 V DC (Attention! Um is no rated voltage.) |
| Output: Contact loading: | 50 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive load |
| Output: Maximum safe voltage: | 253 V AC (Attention! The rated voltage can be lower.) |
| Certificate: | TÜV 99 ATEX 1493 X |
| Output: Marking: | II 3G Ex ec nC IIC T4 Gc |
| Galvanic isolation: Input/input: | not available |
| Galvanic isolation: Input/Output: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 |
| FM approval: FM certificate: | FM19US0207X |
| FM approval: Control drawing: | 116-0035 |
| CSA approval: Control drawing: | 116-0047 |
| IECEx approval: IECEx certificate: | IECEx TUN 19.0013X |
| IECEx approval: IECEx marking: | Ex ec nC IIC T4 Gc |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ТН ВЭД: | |
| Страна происхождения: | ID |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |