128259
VAA-4E4A-CB2-Z/E2
AS-Interface printed circuit board module
The AS-Interface module is ideal for integrating customer-specific electronics, for example light sensors or LED lights. The external auxiliary power supplies all the inputs and outputs, which are short-circuit proof and protected from overload.The connection between display and control elements and the AS-Interface circuit board can be made with screw plug terminals. The connection on the AS-Interface and external auxiliary power supply are also implemented with plug-in screw terminals. Printed circuit board module, encapsulated in housing. 4 inputs/4 outputsfa. An output overload is reported by the "periphery error" to the AS-Interface master. Communication over the AS-Interface remains in effect. Note:. Communication monitoring is integrated to switch the outputs to no current if there is no communication on the AS-Interface line.
| Slave type: | Standard slave |
| AS-Interface specification: | V2.0 |
| Required master specification: | ≥ V2.0 |
| UL File Number: | E223772 |
| LED FAULT: | error display; LED red red: communication error or address is 0 red flashing: overload of outputs |
| LED PWR: | AS-Interface voltage; LED green |
| LED AUX: | ext. auxiliary voltage UAUX ; LED green |
| LED IN: | switching state (input); 4 LED yellow |
| LED OUT: | Switching state (output); 4 LED yellow |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 30 mA |
| Protection class: | III |
| Surge protection: | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
| Number/Type: | 4 inputs for 2- or 3-wire sensors (PNP), DC |
| Supply: | from external auxiliary voltage UAUX |
| Voltage: | 20 ... 30 V DC PELV |
| Input current: | 5 mA (typically) |
| Switching point: | according to EN 61131-2 Typ 1 |
| : 0 (unattenuated): | ≤ 0.5 mA |
| : 1 (attenuated): | ≥ 2 mA |
| Signal delay: | < 2 ms (input/AS-Interface) |
| Signal frequency: | ≤ 250 Hz |
| Number/Type: | 4 electronic outputs, PNP |
| Supply: | from external auxiliary voltage UAUX |
| Voltage: | 20 ... 30 V DC PELV |
| Current: | ≤ 100 mA per output, ≤ 140 mA total |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 EN 61000-6-4:2007 EN 62026-2:2015 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Input: | EN 61131-2:2015 |
| Emitted interference: | EN 61000-6-4:2007 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61326-1:2013 |
| Profile: | S-7.0 |
| IO code: | 7 |
| ID code: | 0 |
| ID1 code: | F |
| ID2 code: | E |
| Data bits (function via AS-Interface): | input output |
| Electromagnetic compatibility: D0: | IN1 OUT1 |
| Electromagnetic compatibility: D1: | IN2 OUT2 |
| Electromagnetic compatibility: D2: | IN3 OUT3 |
| Electromagnetic compatibility: D3: | IN4 OUT4 |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | not used |
| Electromagnetic compatibility: P1: | not used |
| Electromagnetic compatibility: P2: | not used |
| Electromagnetic compatibility: P3: | not used |
| Ambient temperature: | -25 ... 60 °C (-13 ... 140 °F) |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Relative humidity: | 85 % , noncondensing |
| Climatic conditions: | For indoor use only |
| Altitude: | ≤ 2000 m above MSL |
| Pollution degree: | 2 |
| Connection: | screw terminals, removable rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 1.5 mm2 In case of wire end ferrule with plastic sleeve: 0.25 mm2 ... 0.5 mm2 On connection of multiple conductors when using two conductors with the same cross section: Flexible with twin wire end ferrule: |
| Mass: | 90 g |
| Mounting: | Self-adhesive velcro for mounting enclosed |
| Tightening torque of clamping screws: | 0.22 ... 0.25 Nm |
| ТН ВЭД: | |
| Страна происхождения: | SG |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |