127361
VAA-4E4A-CB1-Z/E2
AS-Interface printed circuit board module
The AS-Interface connecting module is ideal for integrating custom electronics, such as illuminated pushbuttons or LED lights. The PCB is supplied with power entirely via AS-Interface. The inputs and outputs are resistant to short circuits and overloading. The display and control elements and AS-Interface are connected via cable strands. Printed circuit board module encapsulated in housing for expansion to 8 inputs/8 outputsfa. A signal indicating an overload of the outputs is transmitted to the AS-Interface master via the "peripheral fault" function. The communication via AS-Interface remains unaffected. Note:. A communication monitoring function is integrated into the system. This function disconnects the outputs from the power supply when no communication is taking place on the AS-Interface line.
| Slave type: | Standard slave |
| AS-Interface specification: | V2.0 |
| Required master specification: | ≥ V2.0 |
| UL File Number: | E223772 |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 30 mA (without sensors) / max. 180 mA |
| Protection class: | III |
| Surge protection: | Ue: Over voltage category III, safe isolated power supplies (PELV) |
| Number/Type: | 4 inputs for 2- or 3-wire sensors (PNP), DC |
| Supply: | from AS-Interface |
| Voltage: | 21 ... 31 V |
| Input current: | ≤ 8 mA (limited internally) |
| Switching point: | according to EN 61131-2 Typ 1 |
| : 0 (unattenuated): | ≤ 1.5 mA |
| : 1 (attenuated): | ≥ 4 mA |
| Number/Type: | 4 electronic outputs, PNP |
| Supply: | from AS-Interface |
| Voltage: | 21 ... 31 V |
| Current: | ≤ 100 mA per output, ≤ 140 mA total |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 EN 61000-6-4:2007 EN 62026-2:2015 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Input: | EN 61131-2:2015 |
| Emitted interference: | EN 61000-6-4:2007 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61326-1:2013 |
| Profile: | S-7.0 |
| IO code: | 7 |
| ID code: | 0 |
| ID1 code: | F |
| ID2 code: | E |
| Data bits (function via AS-Interface): | input output |
| Electromagnetic compatibility: D0: | IN1 OUT1 |
| Electromagnetic compatibility: D1: | IN2 OUT2 |
| Electromagnetic compatibility: D2: | IN3 OUT3 |
| Electromagnetic compatibility: D3: | IN4 OUT4 |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | not used |
| Electromagnetic compatibility: P1: | not used |
| Electromagnetic compatibility: P2: | not used |
| Electromagnetic compatibility: P3: | not used |
| Ambient temperature: | -25 ... 60 °C (-13 ... 140 °F) |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Relative humidity: | 85 % , noncondensing |
| Climatic conditions: | For indoor use only |
| Altitude: | ≤ 2000 m above MSL |
| Pollution degree: | 2 |
| Connection: | screw terminals, removable rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 1.5 mm2 In case of wire end ferrule with plastic sleeve: 0.25 mm2 ... 0.5 mm2 On connection of multiple conductors when using two conductors with the same cross section: Flexible with twin wire end ferrule: |
| Tightening torque of clamping screws: | 0.22 ... 0.25 Nm |
| ТН ВЭД: | |
| Страна происхождения: | SG |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |