Pepperl+Fuchs 072019

KFD2-PT2-Ex1-1

Potentiometer Converter

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

1-channel isolated barrier, 24 V DC supply (Power Rail), Potentiometer input, Voltage output 0 V .. 5 V, Lead resistance compensation adjustment, Accuracy 0.05 %, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. It provides the source voltage to a potentiometer and transfers its wiper position from hazardous areas to safe areas. It then converts the signal to a 0 V .. 5 V voltage output (consistant with 0 mA .. 20mA current output, see for example KFD2-PT2-Ex1-4). The unit can be used in a 3-, 4-, or 5-wire configuration depending on the required measurement accuracy. Terminals 2 and 5 are used as the sense line for the potentiometer lead resistance compensation in a 5-wire configuration. The barrier’s potentiometer can be used to compensate for lead resistance up to 5 % of the hazardous area potentiometer value.

Технические характеристики

Signal type: Analog input
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 11+, 12-
Rated voltage: 20 ... 35 V DC
Ripple: within the supply tolerance
Power dissipation: 0.5 W
Power consumption: 0.6 W
Connection side: field side
Connection: terminals 4-, 5-, 3+, 2+, 1+
Potentiometer: Types of measuring: 3-, 4-, 5-wire technology
Potentiometer: Nominal resistance: 800 Ω to 100 kΩ
Potentiometer: Supply voltage: approx. 4.7 V
Lead resistance: 5 % of the potentiometer resistance (adjustable)
Connection side: control side
Connection: terminals 7-, 8+
Voltage output: 0 ... 5 V
Output resistance: max. 30 Ω
Accuracy: 0.05 %
Deviation: Linearity: ≤ ± 5 mV
Deviation: Influence of ambient temperature: ≤ 0.5 mV/K
Rise time: 10 to 90 % ≤ 8 ms; 10 to 90 % within 1 % of span ≤ 25 ms
Output/power supply: functional insulation, rated insulation voltage 50 V AC
Control elements: potentiometer
Configuration: via potentiometer
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Protection against electrical shock: UL 61010-1
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 120 g
Dimensions: 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: BAS 00 ATEX 7171
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C)
Electromagnetic compatibility: Voltage: 10.4 V DC
Electromagnetic compatibility: Current: 31.4 mA
Electromagnetic compatibility: Power: 82 mW
Supply: Maximum safe voltage: 250 V (Attention! The rated voltage can be lower.)
Output: Maximum safe voltage: 250 V (Attention! The rated voltage can be lower.)
Certificate: TÜV 02 ATEX 1797 X
Output: Marking: II 3G Ex nA II T4
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
FM approval: Control drawing: 116-0129
UL approval: Control drawing: 116-0173 (cULus)
IECEx approval: IECEx certificate: IECEx BAS 10.0060 IECEx BAS 10.0061X
IECEx approval: IECEx marking: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m