KL2712
KL2712 | 2-channel triac output terminal 12…230 V AC
The KL2712 output terminal uses a power switch to control mains voltage from 12 to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 0.5 A. The KL2712 has two independent outputs. Its signal state is indicated by means of light emitting diodes.
| Connection technology: | 4-wire |
| Number of outputs: | 2 x make contacts |
| Nominal voltage: | 12…230 V AC |
| Load type: | ohmic, inductive |
| Max. output current: | 2 x 0.025…0.5 A per channel |
| Frequency range: | 47…63 Hz |
| Surge voltage protection: | > 275 V AC |
| Peak current: | 40 A (16 ms), 1.5 A (30 s) |
| Switch-on time: | 0.1 ms |
| Switch-off time: | T/2 |
| Max. residual voltage: | 1.5 V |
| Electrical isolation: | 500 V (K-bus/field voltage), 3750 V AC (1 min.) |
| Leakage current (OFF state): | typ. 0.8 mA, max. 1.5 mA |
| Current consumption power contacts: | only leakage and load current |
| Current consumption K-bus: | typ. 10 mA |
| Bit width in the process image: | 2 outputs |
| Configuration: | no address or configuration setting |
| Special features: | reverse motors (blinds) |
| Weight: | approx. 55 g |
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Pluggable wiring: | for all KSxxxx Bus Terminals |
| Approvals: | CE, UL, Ex, GL |
| ТН ВЭД: | |
| Страна происхождения: | |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |