Article image KL2712

Beckhoff KL2712

KL2712 | 2-channel triac output terminal 12…230 V AC

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The KL2712 output terminal uses a power switch to control mains voltage from 12 to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 0.5 A. The KL2712 has two independent outputs. Its signal state is indicated by means of light emitting diodes.

Parametry techniczne

Connection technology: 4-wire
Number of outputs: 2 x make contacts
Nominal voltage: 12…230 V AC
Load type: ohmic, inductive
Max. output current: 2 x 0.025…0.5 A per channel
Frequency range: 47…63 Hz
Surge voltage protection: > 275 V AC
Peak current: 40 A (16 ms), 1.5 A (30 s)
Switch-on time: 0.1 ms
Switch-off time: T/2
Max. residual voltage: 1.5 V
Electrical isolation: 500 V (K-bus/field voltage), 3750 V AC (1 min.)
Leakage current (OFF state): typ. 0.8 mA, max. 1.5 mA
Current consumption power contacts: only leakage and load current
Current consumption K-bus: typ. 10 mA
Bit width in the process image: 2 outputs
Configuration: no address or configuration setting
Special features: reverse motors (blinds)
Weight: approx. 55 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all KSxxxx Bus Terminals
Approvals: CE, UL, Ex, GL

Parametry logistyczne

ECCN:
Kraj pochodzenia:
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m