KL1362
KL1362 | 2-channel digital input terminal for break-in alarm
The digital KL1362 input terminal analyses the input signals of break-in sensors with the aid of a current loop. Alarm contacts with a fixed resistance ratio can be monitored safely. In the process image, the state of the sensor is indicated by one bit each. A further bit reports short-circuits or line interruptions. Red or green LEDs indicate the state of the two input bits.
| Connection technology: | 2-wire |
| Specification: | break-in alarm |
| Number of inputs: | 2 |
| Nominal voltage: | 24 V (-15 %/+20 %) |
| “0” signal current: | ≤ 1 mA |
| “1” signal current: | ≥ 1 mA |
| Operating voltage: | 5.1 V |
| Line interruption: | < 0.1 mA |
| Short-circuit: | > 3 mA |
| Cable resistance: | ≤ 200 Ω |
| Input filter: | 3.0 ms |
| Current consumption K-bus: | typ. 35 mA |
| Electrical isolation: | 500 V (K-bus/field potential) |
| Bit width in the process image: | 4 inputs |
| Configuration: | no address or configuration setting |
| Special features: | monitoring of alarm contacts |
| Weight: | approx. 55 g |
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Pluggable wiring: | for all KSxxxx Bus Terminals |
| Approvals/markings: | CE, UL, ATEX, GL |
| Ex marking: | II 3 G Ex nA IIC T4 Gc |
| ТН ВЭД: | |
| Страна происхождения: | |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |