EL6861
EL6861 | 1-channel BACnet MS/TP interface RS485, D-sub connection
The EL6861 serial interface enables the connection of BACnet MS/TP devices (Master-Slave/Token-Passing) via an RS485 interface. Up to 32 MS/TP devices (up to 64 if ultra-low power transceivers are used) can be connected. Use the EL6861 interface only in combination with TwinCAT and CX9020 or higher, since the BACnet MS/TP driver integrated in TwinCAT implements the communication via the MS/TP protocol (BACnet Revision 12). The configuration is also done in TwinCAT.
| Technology: | D-sub, 9-pin |
| Devices: | 32, up to 64 if ultra-low power transceivers are used |
| Data transfer channels: | 1 |
| Data transfer rates: | 9600, 19,200, 38,400, 57,600, 76,800 and 115,200 baud (default: 9600 baud) |
| Interfaces: | 1 x RS485 |
| Termination resistor: | externally via ZB3100 or ZS1031-3000 connector |
| Bias resistor (network bias): | externally via ZB3100 or ZS1031-3000 connector |
| Cable length: | max. 500 m twisted pair |
| Providing external supply: | 1 x max. 5 V/20 mA, out of E-bus supply, short-circuit proof |
| Power supply: | via the E-bus |
| Distributed clocks: | – |
| Electrical isolation: | 500 V (E-bus/signal voltage) |
| Bit width in the process image: | 128 x 8 bit input, 128 x 8 bit output, 16 bit control, 16 bit status |
| Configuration: | configuration via controller, TwinCAT |
| Current consumption power contacts: | – |
| Current consumption E-bus: | typ. 170 mA |
| Special features: | can only be used with TwinCAT |
| Weight: | approx. 55 g |
| Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Approvals: | CE, UL |
| ТН ВЭД: | |
| Страна происхождения: | |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |