EJ3202
EJ3202 | 2-channel analog input PT100 (RTD)
The EJ3202 analog input allows resistance sensors to be connected directly. The EtherCAT plug-in module's circuitry can operate 2- and 3-wire sensors. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The EJ3202’s standard settings are: resolution 0.1 °C in the temperature range of PT100 sensors in 3-wire connection. The EtherCAT plug-in modules indicate their signal state by means of light emitting diodes. Sensor malfunctions such as broken wires are indicated by error LEDs.
| Technology: | 2-wire |
| Sensor types: | PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation) |
| Number of inputs: | 2 |
| Measuring range: | -200…+850 °C (PT sensors); -60…+250 °C (Ni sensors) |
| Resolution: | 0.1 °C per digit |
| Measuring error: | < ±0.5 °C for PT sensors |
| Input filter limit frequency: | typ. 1 kHz |
| Conversion time: | approx. 85 ms default setting, 2…800 ms configurable |
| Distributed clocks: | – |
| Power supply: | via the E-bus |
| Current consumption E-bus: | typ. 165 mA |
| Electrical isolation: | 500 V (E-bus/field potential) |
| Special features: | integrated digital filter, limit value monitoring, variable connection technology |
| Dimensions (W x H x D): | approx. 12 mm x 66 mm x 55 mm |
| Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
| Relative humidity: | 95 %, no condensation |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Approvals/markings: | CE, UL |
| ТН ВЭД: | |
| Страна происхождения: | |
| EAN: | |
| Вес: | 0,00 kg |
| Длина: | 0,00 m |
| Ширина: | 0,00 m |
| Высота: | 0,00 m |