Article image EJ3202

Beckhoff EJ3202

EJ3202 | 2-channel analog input PT100 (RTD)

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The EJ3202 analog input allows resistance sensors to be connected directly. The EtherCAT plug-in module's circuitry can operate 2- and 3-wire sensors. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The EJ3202’s standard settings are: resolution 0.1 °C in the temperature range of PT100 sensors in 3-wire connection. The EtherCAT plug-in modules indicate their signal state by means of light emitting diodes. Sensor malfunctions such as broken wires are indicated by error LEDs.

Parametry techniczne

Technology: 2-wire
Sensor types: PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation)
Number of inputs: 2
Measuring range: -200…+850 °C (PT sensors); -60…+250 °C (Ni sensors)
Resolution: 0.1 °C per digit
Measuring error: < ±0.5 °C for PT sensors
Input filter limit frequency: typ. 1 kHz
Conversion time: approx. 85 ms default setting, 2…800 ms configurable
Distributed clocks:
Power supply: via the E-bus
Current consumption E-bus: typ. 165 mA
Electrical isolation: 500 V (E-bus/field potential)
Special features: integrated digital filter, limit value monitoring, variable connection technology
Dimensions (W x H x D): approx. 12 mm x 66 mm x 55 mm
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Approvals/markings: CE, UL

Parametry logistyczne

ECCN:
Kraj pochodzenia:
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m