This signal conditioner provides the galvanic isolation between field circuits and control circuits. 1-channel signal conditioner, 24 V DC supply, Input for 2- or 3-wire sensors, Input frequency 10 mHz .. 50 kHz, Relay contact output, Start-up override and restart inhibit, Configurable by DIP switches and software, Connection via screw terminalspa. The device monitors the overspeed condition and the underspeed condition of a digital signal. The device has an input for the following digital signals:. Mechanical contacts. 2-wire sensors (NAMUR, SN, DC, S0). 3-wire sensors (NPN, PNP). AC/DC voltage sources (magnetic sensors), custom-specific setting. The input is reverse polarity protected and short-circuit proofed. The connected sensors can also be supplied externally. The device compares the input frequency with a user-specified reference frequency. An overspeed condition or an underspeed condition is signaled via the relay contact outputs. A fault is indicated by a red LED. The device is easily configured by the use of DIP switches or software. The device can be powered via terminals or Power Bus.
| Signal type: | Digital Input |
| Connection: | Power Bus or terminals 1-, 2+ |
| Rated voltage: | 16.8 ... 31.2 V DC |
| Power dissipation: | 0.6 W |
| Power consumption: | 1.1 W |
| Programming interface: | programming socket |
| Connection side: | field side |
| NAMUR sensor: Type: | 2-wire |
| NAMUR sensor: Connection: | terminals 5+, 6 |
| NAMUR sensor: Signal: | acc. to EN 60947-5-6 (NAMUR) |
| NAMUR sensor: Sensor supply: | 8 V |
| NAMUR sensor: Open-circuit: | < 0.1 mA |
| NAMUR sensor: Switching point: | 1.2 ... 2.1 mA |
| NAMUR sensor: Short-circuit: | > 6 mA |
| NAMUR sensor: Input impedance: | 1 kΩ |
| Mechanical contact: Type: | 2-wire |
| Mechanical contact: Connection: | terminals 5+, 6 |
| Mechanical contact: Sensor supply: | 15 V |
| Mechanical contact: External supply: | ≤ 32 V |
| Mechanical contact: Switching point: | 8 ... 10 V / 1.2 ... 2.1 mA |
| Mechanical contact: Frequency: | 0 ... 50 Hz , debounce filter |
| Mechanical contact: Input impedance: | 4 kΩ |
| SN sensor: Type: | 2-wire |
| SN sensor: Connection: | terminals 5+, 6 |
| SN sensor: Sensor supply: | 8 V |
| SN sensor: Open-circuit: | < 0.1 mA |
| SN sensor: Switching point: | 1.2 ... 2.1 mA |
| SN sensor: Short-circuit: | > 6 mA |
| SN sensor: Input impedance: | 1 kΩ |
| 2-wire DC sensor: Type: | 2-wire |
| 2-wire DC sensor: Connection: | terminals 5+, 6 |
| 2-wire DC sensor: Signal: | acc. to EN 60947-5-2 |
| 2-wire DC sensor: Sensor supply: | 16 V / 25 mA , short-circuit protected |
| 2-wire DC sensor: External supply: | ≤ 32 V |
| 2-wire DC sensor: Switching point: | 2 ... 5 mA |
| 2-wire DC sensor: Input impedance: | 1 kΩ |
| S0 sensor: Type: | 2-wire |
| S0 sensor: Connection: | terminals 5+, 6 |
| S0 sensor: Signal: | acc. to EN 62053-31 , Type B |
| S0 sensor: Sensor supply: | 15 V |
| S0 sensor: Switching point: | 0.15 ... 2 mA |
| S0 sensor: Input impedance: | 4 kΩ |
| NPN sensor: Type: | 3-wire |
| NPN sensor: Connection: | terminals 5+, 6, 7- |
| NPN sensor: Signal: | acc. to EN 60947-5-2 |
| NPN sensor: Sensor supply: | 16 V / 25 mA , short-circuit protected |
| NPN sensor: External supply: | ≤ 32 V |
| NPN sensor: Switching point: | 3 ... 5 V |
| NPN sensor: Input impedance: | 4 kΩ |
| PNP sensor: Type: | 3-wire |
| PNP sensor: Connection: | terminals 5+, 6, 7- |
| PNP sensor: Signal: | acc. to EN 60947-5-2 |
| PNP sensor: Sensor supply: | 16 V / 25 mA , short-circuit protected |
| PNP sensor: External supply: | ≤ 32 V |
| PNP sensor: Switching point: | 8 ... 10 V |
| PNP sensor: Input impedance: | 4 kΩ |
| AC/DC voltage source: Connection: | terminals 6, 7- |
| AC/DC voltage source: Signal: | max. ± 30 V |
| AC/DC voltage source: Switching point: | 150 ... 400 mV |
| AC/DC voltage source: Input impedance: | 4 kΩ |
| Function input: Connection: | terminal 8 |
| Function input: Open loop voltage: | 7.5 V |
| Function input: Input impedance: | approx. 50 kΩ |
| Function input: Function 1: | activation start-up override |
| Function input: Switching point: | < 3 V , edge triggered |
| Function input: Adjustment range: | 1 ... 6500 s |
| Function input: Function 2: | reset restart inhibit |
| Function input: Switching point: | > 12 V , edge triggered |
| Connection side: | control side |
| Connection: | terminals 3, 4: |
| Output: | signal, relay |
| Contact loading: | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load |
| Minimum switch current: | 2 mA / 24 V DC |
| Energized/De-energized delay: | ≤ 20 ms / ≤ 20 ms |
| Mechanical life: | 107 switching cycles |
| Accuracy: | max. 0.1 % of the measurement value |
| Measuring time: | ≤ 100 ms |
| Influence of ambient temperature: | < 100 ppm/K of the measured value |
| Frequency range: | 0.01 ... 50000 Hz |
| Output/power supply: | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min |
| Input/Other circuits: | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches via software |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Low voltage: Directive 2014/35/EU: | EN 61010-1:2010 |
| Degree of protection: | IEC 60529:2001 |
| Protection against electrical shock: | EN 61010-1:2010 |
| Ambient temperature: | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Damaging gas: | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Core cross-section: | 0.5 ... 2.5 mm2 (20 ... 14 AWG) |
| Mass: | approx. 60 g |
| Dimensions: | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Optional accessories: | power feed module S1SD-2PF adapter with USB interface S-ADP-USB Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP splitter VAZ-CHAIN-BU/BN70MM/1,0-25 |
| ECCN: | |
| Kraj pochodzenia: | DE |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |