Pepperl+Fuchs 211734

WHA-UT-F7B1-0-PP-Z1-Ex2

WirelessHART

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The device is designed to connect RTDs or thermocouples from the hazardous area and provide the according temperature values into a WirelessHART network. It has an internal cold junction compensation for thermocouples. A fault is indicated by a red flashing LED per NAMUR NE44. The unit is easily configurable with a configuration tool (DTM). For additional information, refer to the manual and www.pepperl-fuchs.com.

Parametry techniczne

Rated voltage: 3.6 V DC , battery operated
Power dissipation/power consumption: < 0.09 W
Connection: terminals 1, 2, 3, 4
RTD: type Pt100, Pt1000 (IEC 751: 1995; GOST: alpha = 0.391)
: Connection: 2-wire: 2 sensors, 3- or 4-wire: 1 sensor
: Lead resistance: max. 10 Ω
: Measurement loop monitoring: sensor breakage
Thermocouples: type E, J, K, T (IEC 584-1)
: Cold junction compensation: internal , external
: Measurement loop monitoring: sensor breakage
: Measurement range: type K: -270 ... 1370 °C type T: -270 ... 400 °C type E: -270 ... 1000 °C type J: -210 ... 1200 °C
Resistor: Measurement range: 0 ... 500 Ω , 0 ... 4000 Ω
Voltage: mV Input
Resistor: Measurement range: -100 ... 100 mV , 0 ... 300 mV
Input resistance: ≥ 1 MΩ
Interface: internal antenna
Output variables: PV: input 1 (°C, Ω, mV) SV: input 2 (°C, Ω, mV) TV: CJC temperature (°C) estimated battery life (days) battery voltage (volts) residual battery capacity (%)
Communication: WirelessHART specifications - physical layer: IEEE 802.15.4.2006 - frequency band: 2.4 GHz (ISM band, licence free) - transmission rate: 250 kBit/s - maximum transmit power: +10 dBm (EIRP) - transmission range: outdoor 250 m, indoor 50 m (under reference conditions) - communication standard: WirelessHART
Temperature measuring range: sensor type: - TC type E: -200 ... 1000 °C, accuracy ± 0,5 °C - TC type J: -200 ... 750 °C, accuracy ± 1 °C - TC type T: -200 ... 400 °C, accuracy ± 1 °C - TC type K: -140 ... 1300 °C, accuracy ± 1 °C - RTD type Pt100: -200 ... 850 °C, accuracy ± 0,5 °C - 100 mV, accuracy ± 20 µV - 300 mV, accuracy ± 40 µV
Accuracy: - internal cold junction compensation error ± 1,5 °C (typ. acc. to IEC 61298-3) - external cold junction compensation error ± 1 °C (typ.) - resolution error < 0.1 °C - accuracy TC ± 20 µV - accuracy RTD: ± 100 mΩ
Display elements: LED PWR (battery status), one green LED LED COM (communication status), one yellow LED LED FLT (fault signal), one red LED
Control elements: 2 push buttons: - power On/Off - Join Trigger - Device Status Trigger - 2-wire RTD Wire Compensation - battery replacement confirmation
Configuration: wired interface: - HART 7.1, FSK compatible - transmission rate: 1200 Bit/s - used for device commissioning with an handheld terminal or a configuration tool (DTM)
Parameter assignment: - sampling period: 1, 2, 5, 10, 30 seconds or 1, 2, 5, 10, 30, 60 minutes - transmit power: configurable 0 dBm or 10 dBm (EIRP) - sensor type - mapping of input measuring values 1 and 2 into primary variable (PV) and secondary variable (SV) - publishing of up to three messages from the device, transmission rate selectable from 4 seconds to 60 minutes
Electromagnetic compatibility: Directive 2004/108/EC: EN 61326-1:2006
Radio and telecommunication terminal equipment: The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning.
Electromagnetic compatibility: Directive 99/5/EC: ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001
Electromagnetic compatibility: FCC CFR47 Part 15 B and C: ANSI C63.4-2003 , FCC ID: SJC-M2140
Degree of protection: IEC 60529
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Accuracy: IEC 61298-3
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -20 ... 70 °C (-4 ... 158 °F)
Relative humidity: 5 ... 95 %, noncondensing
Corrosion resistance: acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60
Degree of protection: IP65
Mass: approx. 1000 g
Dimensions: 77 x 129 x 177 mm (3 x 5.08 x 6.97 inch)
Mounting: panel or pole mounting
EU-type examination certificate: IMQ 09 ATEX 008X
Electromagnetic compatibility: Marking: II 2(1)G Ex ia [ia] IIC T4
Directive conformity: Directive 94/9/EC: EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007
FM approval: CoC 3042534
IECEx approval: IECEx INE 09.0025X
Directive conformity: Approved for: Ex ia IIC T4
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Designation: battery W-BAT-B1-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-F7MK External cold junction compensation W-ACC-CJC

Parametry logistyczne

ECCN:
Kraj pochodzenia: Deutschland
EAN: 4050143061563
Waga: 0,74 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m