288594
VBA-4E-KE5-IL
AS-Interface analog module
Switch cabinet module. 4 analog Inputsfa
| Slave type: | Standard slave |
| AS-Interface specification: | V3.0 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E223772 |
| MTBF: | 173 a |
| LED FAULT: | Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault |
| LED PWR: | AS-Interface voltage; green LED Green: voltage OK Flashing green: address 0 or peripheral error |
| LED AUX: | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| LED IN: | status of input signal; LED yellow off: not active on: signal within measurement range flashing: signal outside of measurement range |
| Auxiliary voltage (output): | 20 ... 30 V DC PELV |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 70 mA |
| Protection class: | III |
| Current consumption: | IAUX ≤ 650 mA |
| Surge protection: | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) |
| Number/Type: | 4 analog inputs Current: 0 mA ... 20 mA/4 mA ... 20 mA |
| Supply: | From auxiliary voltage UAUX |
| Current loading capacity: | ≤ 600 mA From auxiliary voltage UAUX ; overload and short-circuit resistant |
| Input resistance: | current input: max. 70 Ω |
| Accuracy: | 0.1 % of input signal range at 25 °C (298 K) |
| Resolution: | 15 Bit |
| Temperature influence: | 0.0025 %/K of input signal range |
| Temperature influence: | 1 µA/K or 0,3 mV/K |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Emitted interference: | EN 61000-6-4:2007 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
| Profile: | S-7.3.E |
| IO code: | 7 |
| ID code: | 3 |
| ID1 code: | F |
| ID2 code: | E |
| Data bits (function via AS-Interface): | The transfer of the data value is based on AS-Interface Profile 7.3. |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | 50/60 Hz filter P0=1, enabled P0=0, disabled |
| Electromagnetic compatibility: P1: | not used |
| Electromagnetic compatibility: P2: | Indication of the peripheral fault by exceeding measuring range P2=1, peripheral fault is reported P2=0, peripheral fault is not reported |
| Electromagnetic compatibility: P3: | P3=1, wire break detection active P3=0, wire break detection disabled |
| Ambient temperature: | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 85 % , noncondensing |
| Climatic conditions: | For indoor use only |
| Altitude: | ≤ 2000 m above MSL |
| Shock and impact resistance: | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
| Vibration resistance: | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Pollution degree: | 2 |
| Degree of protection: | IP20 |
| Connection: | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 |
| Material: Housing: | PA 66-FR |
| Mass: | 110 g |
| Mounting: | DIN mounting rail |
| Note: | Max. length of jumpers = 5 cm |
| ECCN: | |
| País de origen: | SG |
| EAN: | |
| Peso: | 0,14 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |