276874
MB-FB-GTR1
Fieldbus Power Hub, Gateway Motherboard
For 2 gateway modules, For PROFIBUS PA, Redundant configuration, Installation in Zone 2/Class I, Div. 2, Spring terminals or screw terminals selectablepa
| Design / Mounting: | Motherboard based |
| Rated voltage: | 19.2 ... 35 V SELV/PELV |
| Rated current: | 2 ... 3 A |
| Fault signal: | VFC alarm output via connectors |
| Rotary switch: | bus addressing, gateway-specific |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 |
| Electromagnetic compatibility: | NE 21:2011 |
| Degree of protection: | IEC 60529 |
| Fieldbus standard: | IEC 61158-2 |
| Shock resistance: | EN 60068-2-27 |
| Vibration resistance: | EN 60068-2-6 |
| Ambient temperature: | -40 ... 70 °C (-40 ... 158 °F) |
| Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
| Relative humidity: | < 95 % non-condensing |
| Shock resistance: | 15 g 11 ms |
| Vibration resistance: | 1 g , 10 ... 150 Hz |
| Pollution degree: | max. 2, according to IEC 60664 |
| Corrosion resistance: | acc. to ISA-S71.04-1985, severity level G3 |
| Housing material: | Polycarbonate |
| Degree of protection: | IP20 |
| Mass: | approx. 300 g |
| Mounting: | DIN mounting rail |
| Certificate: | TÜV 15 ATEX 7735 X |
| Electromagnetic compatibility: Marking: | II 3 G Ex ec IIC T4 Gc |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 |
| IECEx approval: | IECEx TUR 16.0007X |
| Directive conformity: Approved for: | Ex ec IIC T4 Gc |
| Marine approval: | pending |
| ECCN: | |
| País de origen: | Singapur |
| EAN: | 4050143075928 |
| Peso: | 0,56 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |