276337
FB6210ER
Digital Output with Shutdown Input
4-channel, Outputs Ex ia, Installation in suitable enclosures in Zone 1, Module can be exchanged under voltage (hot swap)pa
| Occupied slots: | 2 |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | backplane bus / booster terminals |
| Rated voltage: | 12 V DC , only in connection with the power supplies FB92** |
| Input voltage range: | 18.5 ... 32 V DC (SELV/PELV) booster voltage |
| Power dissipation: | 3 W |
| Power consumption: | 0.15 W |
| Connection: | backplane bus |
| Interface: | manufacturer-specific bus to standard com unit |
| Number of channels: | 4 |
| Suitable field devices: Field device: | Solenoid Valve |
| Suitable field devices: Field device [2]: | audible alarm |
| Suitable field devices: Field device [3]: | visual alarm |
| Connection: | channel I: 9+, 10-; channel II: 11+, 12-; channel III: 13+, 14-; channel IV: 15+, 16- |
| Current limit: | 37 mA |
| Internal resistor: | max. 370 Ω |
| Open loop voltage: | 24.5 V |
| Line fault detection: | can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms) |
| Suitable field devices: Short-circuit: | < 100 Ω |
| Suitable field devices: Open-circuit: | > 15 kΩ |
| Response time: | 10 ms (depending on bus cycle time) |
| Watchdog: | within 0.5 s the device goes in safe state, e.g. after loss of communication |
| Reaction time: | 10 s |
| LED indication: | LED green: supply LED red: line fault , red flashing: communication error |
| Coding: | optional mechanical coding via front socket |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1 |
| Electromagnetic compatibility: | NE 21 |
| Degree of protection: | IEC 60529 |
| Environmental test: | EN 60068-2-14 |
| Shock resistance: | EN 60068-2-27 |
| Vibration resistance: | EN 60068-2-6 |
| Damaging gas: | EN 60068-2-42 |
| Relative humidity: | EN 60068-2-56 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 95 % non-condensing |
| Shock resistance: | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
| Vibration resistance: | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
| Damaging gas: | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection: | IP20 (module) , a separate housing is required acc. to the system description |
| Connection: | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) |
| Mass: | approx. 750 g |
| Dimensions: | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
| EU-type examination certificate: | PTB 97 ATEX 1074 U |
| Electromagnetic compatibility: Marking: | II 2(1) G Ex d [ia Ga] IIC Gb II (1) D [Ex ia Da] IIIC |
| Output: Voltage: | 27.8 V |
| Output: Current: | 90.4 mA |
| Output: Power: | 629 mW |
| Output: Internal capacitance: | 2.5 nF |
| Output: Internal inductance: | 0 mH |
| Galvanic isolation: Output/power supply, internal bus: | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 |
| ATEX approval: | PTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U |
| EAC approval: | Russia: RU C-IT.MIII06.B.00129 |
| Marine approval: Lloyd Register: | 15/20021 |
| Marine approval: DNV GL Marine: | TAA0000034 |
| Marine approval: American Bureau of Shipping: | T1450280/UN |
| Marine approval: Bureau Veritas Marine: | 22449/B0 BV |
| System information: | The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate. |
| Supplementary information: | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| País de origen: | Deutschland |
| EAN: | 4050143075904 |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |