Pepperl+Fuchs 263813

VBA-4E4A-KE5-ZEJQ/E2L

AS-Interface sensor/actuator module

Bajo pedido. Envíenos un correo electrónico para consultar el precio y la disponibilidad.
"ucnguBrctvdgcxgt0eqo"

Descripción

Cabinet module. 4 inputs and 4 outputsfa

Parámetros técnicos

Slave type: A/B slave
AS-Interface specification: V3.0
Required master specification: ≥ V3.0
UL File Number: E223772
MTBF: 141 a
LED FAULT: Error display; red LED red: communication error, i.e. address is 0 red flashing: overload internal input supply, i.e. overload or lead interruption outputs
LED INT: Internal input supply active; LED green
LED PWR: AS-Interface voltage; green LED green: voltage OK flashing green: address 0
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED IN: switching state (input); 4 LED yellow
LED OUT: switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption
Auxiliary voltage (input): 12 ... 30 V DC PELV
Auxiliary voltage (output): 20 ... 30 V DC PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 35 mA (without sensors) / max. 190 mA
Protection class: III
Surge protection: UEXT, UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) Overvoltage category of the power supplies (primary): III
Rated insulation voltage: 92 V
Pulse withstand voltage: 0.8 kV
Number/Type: 4 inputs for 3-wire sensors (PNP), DC
Supply: from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage: 21 ... 31 V DC (INT)
Current loading capacity: ≤ 150 mA, overload- and short-circuit protected (INT)
Input current: ≤ 5.6 mA (max.)
Switching point: according to DIN EN 61131-2 (type 1)
: 0 (unattenuated): ≤ 0.5 mA
: 1 (attenuated): ≥ 2 mA
Signal delay: < 1 ms (input/AS-Interface)
Number/Type: 4 electronic outputs, PNP, overload and short-circuit proof
Supply: from external auxiliary voltage UAUX
Current: 2 A Per output, total 4 A (TB ≤ 60 °C) 1 A Per output, total 4 A (TB ≤ 70 °C)
Voltage: ≥ (UAUX - 0.5 V)
Usage category: DC-13
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Machinery Directive: Directive 2006/42/EC: EN ISO 13849-1:2008 EN ISO 13849-2:2012
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Electrical safety: IEC 61140:2009
Input: EN 61131-2:2004
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Functional safety: EN ISO 13849-1:2008 EN ISO 13849-2:2012
Profile: S-7.A.7
IO code: 7
ID code: A
ID1 code: 7
ID2 code: 7
Data bits (function via AS-Interface): input output
Machinery Directive: D0: IN1 O1
Machinery Directive: D1: IN2 O2
Machinery Directive: D2: IN3 O3
Machinery Directive: D3: IN4 O4
Parameter bits (programmable via AS-i): function
Machinery Directive: P0: Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
Machinery Directive: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Machinery Directive: P2: Lead breakage outputs P2 = 0 lead breakage on P2 = 1 lead breakage off (default settings)
Machinery Directive: P3: not used
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Shock and impact resistance: 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance: 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree: 2
Degree of protection: IP20 For safety applications: Installation in an enclosure with a minimum protection class of IP54 required
Connection: Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material: Housing: PA 66-FR
Mass: 110 g
Mounting: DIN mounting rail

Parámetros logísticos

ECCN:
País de origen: SG
EAN:
Peso: 0,00 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m